14.10 Process controller funcon selecon
By means of the following funcons, the response of the inverter can be controlled when PID
control is acvated. 4Conguring the process controller ^ 407
Parameter Name / value range / [default seng] Info
0x2631:045
(P400.45)
Funcon list: Deacvate PID controller
(Funcon list: PID o)
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 532
Assignment of a trigger for the "Deacvate PID controller" funcon.
Trigger = TRUE: If PID control is acvated, ignore PID control and drive
the motor in speed-controlled manner.
Trigger = FALSE: If PID control is acvated, drive the motor with PID con-
trol.
Notes:
The PID control mode can be selected in 0x4020:001 (P600.01).
0 Not connected
0x2631:046
(P400.46)
Funcon list: Set process controller output to 0
(Funcon list: PID output=0)
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 532
Assignment of a trigger for the "Set process controller output to 0" func-
on.
Trigger = TRUE: If PID control is acvated, I component and the output of
the PID controller are set to 0 and the internal control algorithm is stop-
ped. The PID control remains acve.
Trigger = FALSE: no acon / deacvate funcon again.
0 Not connected
0x2631:047
(P400.47)
Funcon list: Inhibit process controller I-component
(Funcon list: PID-I inhibited)
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 532
Assignment of a trigger for the "Inhibit process controller I-component"
funcon.
Trigger = TRUE: If PID control is acvated, the I component of the PID
controller is set to 0 and the integraon process is stopped.
Trigger = FALSE: no acon / deacvate funcon again.
Notes:
The reset me can be set in 0x4049 (P602.00).
0 Not connected
0x2631:048
(P400.48)
Funcon list: Acvate PID inuence ramp
(Funcon list: PID-Inf ramp on)
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 532
Assignment of a trigger for the "Acvate PID inuence ramp" funcon.
Trigger = TRUE: the inuence of the process controller is shown via a
ramp.
Trigger = FALSE or not connected: the inuence of the process controller
is hidden via ramp.
Notes:
The inuence of the process controller is always acve (not only when
PID control is acvated).
Acceleraon me for showing the inuence of the process controller
can be set in 0x404C:001 (P607.01).
Deceleraon me for hiding the inuence of the process controller
can be set in 0x404C:002 (P607.02).
1 Constant TRUE
0x4020:001
(P600.01)
Process controller setup (PID): Operang mode
(PID setup: Operang mode)
Selecon of the process controller operang mode.
0 Inhibited Process controller deacvated.
1 Normal operaon The setpoint is higher than the fed back variable (actual value). If the sys-
tem deviaon increases, the motor speed is increased.
Example: pressure-controlled booster pumps (increase in the motor
speed produces an increase in pressure.)
2 Reverse operaon The setpoint is lower than the fed back variable (actual value). If the sys-
tem deviaon increases, the motor speed is increased.
Example: temperature-controlled cooling water pump (increase in motor
speed produces decrease in temperature.)
3 Normal bi-dreconal The direcon of rotaon corresponds to the sign of the system devia-
on. If the system deviaon increases, the motor speed is increased.
4 Reverse bi-direconal A negave system deviaon causes a posive direcon of rotaon. If the
system deviaon increases, the motor speed is increased.
0x4049
(P602.00)
PID I- component
(PID I- component)
10 ... [400] ... 6000 ms
Reset me for system deviaon.
With the seng "6000 ms", the I component is deacvated.
The I component can also be deacvated via the "Inhibit process con-
troller I-component" 0x2631:047 (P400.47) funcon.
0x404C:001
(P607.01)
PID inuence: Acceleraon me for acvaon
(PID inuence: Acvaon me)
0.0 ... [5.0] ... 999.9 s
If the trigger assigned in 0x2631:048 (P400.48) of the "Acvate PID inu-
ence ramp" funcon is TRUE, the inuence of the process controller is
shown by means of a ramp with the acceleraon me set here.
0x404C:002
(P607.02)
PID inuence: Deceleraon me for masking out
(PID inuence: Mask out me)
0.0 ... [5.0] ... 999.9 s
If the trigger assigned in 0x2631:048 (P400.48) of the "Acvate PID inu-
ence ramp" funcon is FALSE, the inuence of the process controller is
hidden via a ramp with the deceleraon me set here.
Flexible I/O conguraon
Process controller funcon selecon
585