9.7 EtherNet/IP
EtherNet/IP™ (EtherNet Industrial Protocol) is a eldbus based on Ethernet which uses the
Common Industrial Protocol™ (CIP™) for data exchange.
•
EtherNet/IP™ andCommon Industrial Protocol™ (CIP™) are trademarks and patented tech-
nologies, licensed by the user organisaon ODVA (Open DeviceNet Vendor Assoziaon),
USA.
•
Detailed informaon on EtherNet/IP can be found on the web page of the user organisa-
on: hp://www.odva.org
•
Informaon on the dimensioning of a EtherNet/IP network can be found in the congura-
on document for the product.
The inverter can be controlled by every CIP Generic Master that either uses "Class 1 Messag-
ing" or "Class 3 Messaging".
For this purpose, the inverter must be congured as AC drive Adapter with the programming
soware »RSLogix™ 5000« from the Rockwell Automaon® Corporaon.
Registered trademarks used or trademarks of the Rockwell Automaon® Corporaon, USA:
•
»RSLogix™«, »RSLogix™ 5000«
•
»Allen-Bradley®«
•
»CompactLogix™«, »ControlLogix®«, »SoLogix™«
Condions for commissioning
•
The control unit (CU) of the inverter is provided with EtherNet/IP (from rmware 02.01).
•
The device is networked as EtherNet/IPAdapter with an EtherNet/IP Scanner and, if neces-
sary, further EtherNet/IP nodes, see "Typical topologies" in the secon 4EtherNet/IP^ 68.
•
An Engineering PC with the programming soware »RSLogix™ 5000« (from version 20) is
connected to the Scanner.
•
Current device descripon les for EtherNet/IP are available.
•
EDS les for Lenze devices: Download
•
The les are installed via the "EDS Hardware Installaon Tool" of the »RSLogix™ 5000«.
•
Allen-Bradley control systems do not need any EDS les to add devices to their congu-
raon.
•
An »RSLogix™ 5000« project has been created and is in the oine state.
•
The CPU and Ethernet adapter of the PLC (Scanner) have been congured.
•
All EtherNet/IP nodes are supplied with voltage and are switched on.
Commissioning with »RSLogix™ 5000« (from version 20)
The basic commissioning steps can be found under:
4Short setup ^ 346
Conguring the network
EtherNet/IP
316