4.2.6.2 Fusing and terminal data
Fuse data
Inverter I55AE137F
I55AE155F
I55AE175F
I55AE211F
I55AE215F
I55AE222F
I55AE230F
I55AE240F
I55AE255F
I55AE275F
I55AE311F
Cable installaon in compliance with EN 60204-1
Installaon method B2
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 16 25 32
Circuit breaker
Characteriscs B
Max. rated current A 10 16 25 32
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 16 25 32
Circuit breaker
Characteriscs B
Max. rated current A 10 16 25 32
Earth-leakage circuit breaker
3-phase mains connecon ≥ 30 mA, type B ≥ 300 mA, type B
Fuse data
Inverter I55AE315F
I55AE318F
I55AE322F
I55AE330F I55AE337F I55AE345F
Cable installaon in compliance with EN 60204-1
Installaon method B2 C
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL -
Max. rated current A 63 - - -
Circuit breaker
Characteriscs B -
Max. rated current A 63 - - -
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 63 80 100 125
Circuit breaker
Characteriscs B
Max. rated current A 63 80 100 125
Earth-leakage circuit breaker
3-phase mains connecon ≥ 300 mA, type B
Electrical installaon
Mains connecon
3-phase mains connecon 480 V
53