EasyManuals Logo

Lenze i55 Series User Manual

Lenze i55 Series
702 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #290 background image
Variable mapping
Via 0x232B:001 ... 0x232B:024 (P530.01 ... 24), 24 registers can be mapped to parameters
of the inverter.
Format: 0xiiiiss00 (iiii = index hexadecimal, ss = subindex hexadecimal)
The display of the internal Modbus register numbers in 0x232C:001 ... 0x232C:024
(P531.01 ... 24) is generated automacally. Since 32-bit parameters require two registers,
there is no 1:1 assignment.
For the mappable registers, a CRC (Cyclic Redundancy Check) is executed. The checksum
determined is displayed in 0x232D (P532.00). The user can read this "validaon code" and
use it for comparison in the Modbus master. In this way it can be checked whether the
inverter currently queried is congured correctly for the respecve applicaon.
Parameter Name / value range / [default seng] Info
0x232B:001 ...
0x232B:024
(P530.01 ... 24)
Modbus parameter mapping: Parameter 1 ... Parame-
ter 24
(Para. mapping: Parameter 1 ... Parameter 24)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entries for Modbus register 40103 ... 40149.
Format: 0xiiiiss00 (iiii = index, ss = subindex)
0x232C:001 ...
0x232C:024
(P531.01 ... 24)
Modbus register assignment: Register 1 ... Register 24
(Reg. assigned: Register 1 ... Register 24)
Read only
Display of the internal Modbus register number starng from which the
parameter mapped in 0x232B:001 ... 0x232B:024 (P530.01 ... 24) is
stored.
For the rst parameter mapped, always 2500.
From the second parameter mapped, 2500 + oset. The oset results
from the data types of the previously mapped parameters.
0x232D
(P532.00)
Modbus vericaon code
(Vericaoncode)
Read only
9.5.9 LED status displays
Informaon about the Modbus status can be obtained quickly via the "MOD-RUN" and "MOD-
ERR" LED displays on the front of the inverter.
The meaning can be seen from the tables below.
Inverter not acve on the Modbus bus (yet)
LED "MOD-RUN" LED "MOD-ERR" Meaning
o on
Internal error
Both LEDs are ickering alternately
Automac detecon of baud rate and data format acve.
Inverter acve on the Modbus
The green "MOD-RUN" LED indicates the communicaon status:
LED "MOD-RUN" Communicaon status
o No recepon / no transmission
on
Recepon / transmission acve
The red "MOD-ERR" LED indicates an error:
LED "MOD-ERR" Error
o No fault
Blinking
Communicaon error
Conguring the network
Modbus RTU
LED status displays
290

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55 Series and is the answer not in the manual?

Lenze i55 Series Specifications

General IconGeneral
BrandLenze
Modeli55 Series
CategoryInverter
LanguageEnglish

Related product manuals