8.2.5.1 Stall monitoring
The stalling monitoring for the sensorless control for synchronous motors (SL-PSM) switches
o the drive if the motor is about to "stall". A possible cause may be an overload of the motor.
Precondions
The stalling monitoring only works in the controlled area and if the motor is not operated in
the eld weakening range.
Details
In order to detect the motor stalling, the cosine phi is used.
Example:
•
For the cosine phi, the value "0.9" is set in 0x2C01:008 (P320.08) according to the data
given on the motor nameplate.
•
The limit value for stalling monitoring is set in 0x2C11:006 to "80 %".
•
Stalling monitoring is triggered if the current cosine phi is lower than 0.72 (80 % of 0.9).
If stalling monitoring is triggered, the "Trouble" error response takes place. If
the operang mode "MS: Velocity mode [-2]" is set in 0x6060 (P301.00), the
motor automacally restarts if the trouble does not exist anymore.
Parameter Name / value range / [default seng] Info
0x2C11:006 High speed range: Stall monitoring limit
0 ... [50] ... 65535 %
•
From version 04.00
The stall monitoring limit refers to the cosine phi of the motor in per-
cent.
0x6060
(P301.00)
Modes of operaon
(Modes of op.)
•
Seng can only be changed if the inverter is inhibi-
ted.
Selecon of the operang mode.
-2 MS: Velocity mode Vendor specic velocity mode
-1 MS: Torque mode (from version 03.00) Vendor specic torque mode
•
Only possible in motor control type 0x2C00 (P300.00) = "Sensorless
vector control (SLVC) [4]" or "Servo control (SC ASM) [2]".
4Torque control w/ freq. limit ^ 206
0 No mode change/no mode assigned No operang mode (standsll)
2 CiA: Velocity mode CiA 402 velocity mode
Motor control
Motor control selecon
Sensorless control for synchronous motors (SL-PSM)
181