Parameter Name / value range / [default seng] Info
0x2949:002
(P337.02)
Negave torque limit source
(Neg. torqlim src)
•
From version 03.00
Selecon of the source for the negave torque limit source.
0 (-) Max torque Negave torque limit source = (-) Max torque 0x6072 (P326.00).
1 Fixed Limit 0.0 % Negave torque limit source = 0.0 %.
2 Analog Input 1 The negave torque limit source is dened as analog signal via the ana-
log input 1.
4Analog input 1 ^ 597
3 Analog Input 2 The negave torque limit source is dened as analog signal via the ana-
log input 2.
4Analog input 2 ^ 601
4 Negave torque limit Negave torque limit source = Negave torque limit 0x60E1.
5 Network target torque The negave torque limit source is dened as process data object via
network.
4Conguring the network ^ 226
0x2949:003
(P337.03)
Actual posive torque limit
(Act postorqlim)
•
Read only: x.x %
•
From version 03.00
Display of the current posive torque limit.
•
100 % ≡ Motor rated torque 0x6076 (P325.00)
0x2949:004
(P337.04)
Actual negave torque limit
(Act negtorqlim)
•
Read only: x.x %
•
From version 03.00
Display of the current negave torque limit.
•
100 % ≡ Motor rated torque 0x6076 (P325.00)
0x2DD5 Torque setpoint
•
Read only: x.xx Nm
•
From version 03.00
Display of the current torque setpoint.
8.4.4.9 Slip controller
In case of V/f characterisc control with feedback (VFC closed loop), the slip is calculated and
injected by the slip controller. The default seng of the slip controller provides robustness
and moderate dynamics.
Precondions
In 0x2C00 (P300.00), the motor control type "V/f characterisc control (VFC closed loop) [7]"
is selected and congured. For details, see chapter "V/f characterisc control (VFC closed
loop)". ^ 172
Details
•
The slip controller is designed as PI controller.
•
In order to improve the response to setpoint changes, the setpoint speed of setpoint fre-
quency is added as feedforward control value to the output (correcng variable) of the slip
controller.
•
With the seng 0x2B14:003 = 0 Hz, the slip controller is deacvated.
Parameter Name / value range / [default seng] Info
0x2B14:001 Gain
0.000 ... [0.100] ... 65.535
Gain of the slip controller.
0x2B14:002 Reset me
0.0 ... [100.0] ... 6553.5 ms
Reset me of the slip controller.
0x2B14:003 Frequency limitaon
0.00 ... [10.00] ... 100.00 Hz
Frequency limitaon of the slip controller.
•
With the seng of 0 Hz, the slip controller is deacvated.
Motor control
Opmisaon of the control loops
Motor controller sengs