9.11.2 Basic sengs
Each network node must be provided with a unique node address (node ID).
Seng the node address
The node address can be set in 0x23C1:004 or via the two rotary encoder switches on the
front of the inverter.
•
If both rotary encoder switches are set to "0", the value set in 0x23C1:004 is used as node
address.
•
The seng that is acve when the inverter is switched on is the eecve seng.
•
A value changed during operaon only gets valid when the device is restarted.
•
Valid node addresses for controlled nodes: 1 ... 239
•
The resulng IP address is "192.168.100.[node address]".
Example: Seng of the node address 52 via the rotary encoder switches
•
52 = 3 x 16 + 4 x 1
•
The resulng IP address is "192.168.100.52".
Note: If the value set via the rotary encoder switches is higher than 239, the node address is
set to 239.
Diagnosc parameters:
•
0x23C2:004 displays the acve node address.
•
0x23C3 displays the switch seng at the last mains switching.
Parameter Name / value range / [default seng] Info
0x23C1:004 POWERLINK sengs: Node ID
0 ... [0] ... 255
Seng of the unique node address (node ID) in the network.
•
The node address set here is only eecve if both rotary encoder
switches are set to "0".
•
In the default seng "0", the rotary encoder switch seng is used.
•
The resulng IP address is "192.168.100.[node address]".
•
A changed node address only becomes eecve aer a restart of the
device.
0x23C2:004 Acve POWERLINK sengs: Node ID
•
Read only
Display of the acve node address (node ID) in the network.
0x23C3 POWERLINK switch posion
•
Read only
Display of the rotary encoder switch seng at the last mains power-on.
Conguring the network
POWERLINK
Basic sengs