9.5.12 Short setup
In the following, the steps required for controlling the inverter via Modbus are described.
Parameterisaon required
1.
Acvate network control: 0x2631:037 (P400.37) = "TRUE [1]"
2.
Set network as standard setpoint source: 0x2860:001 (P201.01) = "Network [5]"
3.
Set Modbus node address.
•
Each network node must be provided with a unique node address.
•
Details: 4Node address seng ^ 282
4.
Set Modbus baud rate.
•
Default seng: Automac detecon.
•
If the automac baud rate detecon funcon is acvated, the rst 5 ... 10 messages
are lost aer switch-on.
•
Details: 4Baud rate
seng ^ 283
5.
Set Modbus data format.
•
Default seng: Automac detecon.
•
If the automac data format detecon funcon is acvated, the rst 5 ... 10 messages
are lost aer switch-on.
•
Details: 4Data format seng ^ 283
6.
Save parameter sengs: 0x2022:003 (P700.03) = "on / start [1]".
7.
Switch the inverter o and then on again in order that the changed communicaon set-
tings can get eecve.
In the default seng, the digital input DI1 is assigned with the "Run" funcon. If
the network control is acvated, this funcon serves as "start enable" for start
commands via network. Hence, the digital input DI1 must be set to HIGH level in
order that the motor can be started via network. 4Start / stop motor ^ 531
Starng/stopping the drive via Modbus
For starng/stopping the drive, Modbus register 42101 can be used.
•
Modbus register 42101 is permanently assigned to the AC Drive control word 0x400B:001
(P592.01).
•
In the frame, the leading 4 is omied in the addressing process. The numbering of the reg-
isters starts with 1; addressing, however starts with 0. Therefore the address 2100
(0x0834) is used in the frame when register 42101 is wrien.
Bits set in the AC drive control word:
•
Bit 0 ≡ Run forward (CW)
•
Bit 5 ≡ Acvate network control
•
Bit 6 ≡ Acvate network setpoint
Example of an inverter with the node address 1:
Request frame by the master
Slave address Funcon code Data Checksum (CRC)
Register address AC Drive control word
0x01 0x06 0x08 0x34 0x00 0x61 0x0B 0x8C
If digital input DI1 ("Start enable") is set to HIGH level, the drive should start and the inverter
should respond with the same frame as conrmaon:
Response message from the inverter
Slave address Funcon code Data Checksum (CRC)
Register address AC Drive control word
0x01 0x06 0x08 0x34 0x00 0x61 0x0B 0x8C
Conguring the network
Modbus RTU
Short setup
292