Parameter Name / value range / [default seng] Info
0x1008 NMT_ManufactDevName_VS
Read only
Display of the manufacturer device name.
0x1009 NMT_ManufactHwVers_VS
Read only
Display of the manufacturer hardware version.
0x100A NMT_ManufactSwVers_VS
Read only
Display of the manufacturer soware version.
0x1018:001 NMT_IdentyObject_REC: VendorId_U32
Read only
Display of the manufacturer's idencaon number.
0x23C2:001 Acve POWERLINK sengs: IP address
Read only
Display of the acve IP address.
0x23C2:002 Acve POWERLINK sengs: Subnet
Read only
Display of the acve subnet mask.
0x23C2:003 Acve POWERLINK sengs: Gateway
Read only
Display of the IP address of the router that connects the POWERLINK
segment to the higher-level network.
0x23C2:004 Acve POWERLINK sengs: Node ID
Read only
Display of the acve node address (node ID) in the network.
0x23C2:005 Acve POWERLINK sengs: MAC Address
Read only
Display of the acve MAC address.
0x23C2:007 Acve POWERLINK sengs: Tx length
Read only
Display of the length of the transmied cyclic data in bytes.
0x23C2:008 Acve POWERLINK sengs: Rx length
Read only
Display of the length of the received cyclic data in bytes.
0x23C3 POWERLINK switch posion
Read only
Display of the rotary encoder switch seng at the last mains power-on.
0x23C8:001 POWERLINK status: Network management
Read only
Display of the current bus status.
0x23C9:001 POWERLINK error: Error
Read only
Bit coded display of the bus error state reported by the LED "BE" (Bus
Error).
Bit 0 = 0 (0x0000) ≡ no bus error
Bit 0 = 1 (0x0001) ≡ acve bus error
Related topics
4POWERLINK ^ 396
6.2.5 Diagnoscs of the inputs and outputs
6.2.5.1 Digital inputs and outputs
The following parameters serve to diagnose the digital inputs and outputs of the inverter.
Parameter Name / value range / [default seng] Info
0x60FD
(P118.00)
Digital inputs
(Digital inputs)
Read only
Bit coded display of the current state of the digital inputs
Bit 16 Level from digital input 1 0 ≡ LOW level, 1 ≡ HIGH level.
Digital input 6 and digital input 7 are only available with applicaon I/O.
Bit 17 Level from digital input 2
Bit 18 Level from digital input 3
Bit 19 Level from digital input 4
Bit 20 Level from digital input 5
Bit 21 Level from digital input 6
Bit 22 Level from digital input 7
Bit 25 Internal interconnecon of digital inputs 0 ≡ digital input terminals are set to HIGH level via pull-up resistors.
1 ≡ digital input terminals are set to LOW level via pull-down resistors.
0x2DAD
(P120.00)
Internal hardware states
(Int. HW states)
Read only
Bit-coded display of internal hardware states.
Bit 0 Relay 0 ≡ X9/NO-COM open and NC-COM closed.
1 ≡ X9/NO-COM closed and NC-COM open.
Bit 1 Digital output 1 0 ≡ LOW level, 1 ≡ HIGH level.
Bit 2 Digital output 2
Bit 10 Charge Relay 1 ≡ precharging of the DC bus via charge relay is acve.
Diagnoscs and fault eliminaon
Diagnoscs parameter
Network diagnoscs