9.10.3 LED status displays
Informaon on the network status can be obtained quickly via the "BUS RDY" and "BUS ERR"
LED displays on the front of the inverter. In addion, the LEDs at the RJ45 sockets indicate the
EtherCAT connecon status.
The meaning of the "BUS RDY" and "BUS ERR" LEDs can be obtained from the following two
tables.
LED "BUS RDY" (green) EtherCAT status Status/meaning
o o / Init The network opon is not acve at the network or is in the "Init" status.
blinking
Pre-Operaonal Access to parameters and objects possible. No process data exchange.
Safe-Operaonal The data is not acve yet in the standard device.
on
Operaonal The network opon works correctly.
ickers
Bootstrap Firmware update of the network opon acve.
LED "BUS ERR" (red) Status/meaning
o No fault
ickers
Local error. The network opon changes automacally to the "Safe-Operaonal" status.
on (red)
A "Sync Manager Watchdog Timeout" has occurred.
blinking
The conguraon is invalid/incorrect.
The LED "L/A" at the RJ45 sockets show the connecon status to the network:
LED "L/A" (green) Status/meaning
o No connecon to the network.
ickers
Data is exchanged via the network.
on
A physical connecon to the network is available.
9.10.4 Diagnoscs
The parameters for diagnosing the network are described below.
Parameter Name / value range / [default seng] Info
0x2362:004
(P511.04)
Acve EtherCAT sengs: Device idener
(EtherCAT diag.: Device ident.)
Read only
From version 02.00
Display of the clear device address in the network which is dened via
rotary encoder switch or object 0x2361:004 (P510.04).
0x2362:006
(P511.06)
Acve EtherCAT sengs: Staon address
(EtherCAT diag.: Staon address)
Read only
From version 02.00
Display of the acve staon address.
0x2362:007
(P511.07)
Acve EtherCAT sengs: Tx length
(EtherCAT diag.: Tx length)
Read only
From version 02.00
Display of the length of the transmied cyclic data in bytes.
0x2362:008
(P511.08)
Acve EtherCAT sengs: Rx length
(EtherCAT diag.: Rx length)
Read only
From version 02.00
Display of the length of the received cyclic data in bytes.
Conguring the network
EtherCAT
LED status displays