14.9.3 Example 3: Acvaon if the selecon is changed (only if the inverter is disabled)
Acvaon method 0x4046 (P755.00) = "If the selecon is changed (disable required) [2]":
•
Switches S3 and S4 serve to select the parameter set (see the following table). At the same
me, the change-over is acvated by a status change of the selecon inputs.
•
Change-over is only possible if the motor is not started (switch S1 open).
•
Switch S2 ("Load parameter set") is ignored in this conguraon.
Connecon plan funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2 S3 S4
Switch S1 Run
Switch S2 Load parameter set (is ignored in this congura-
on)
Switches S3 ... S4 Parameter set selecon and acvaon at the
same me:
S3 S4
O O Parameter set 1
On O Parameter set 2
O On Parameter set 3
On On Parameter set 4
Parameter Name Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:013 (P400.13) Reverse rotaonal direcon Not connected [0]
0x2631:018 (P400.18) Acvate preset (bit 0) Not connected [0]
0x2631:040 (P400.40) Load parameter set Digital input 2 [12]
0x2631:041 (P400.41) Select parameter set (bit 0) Digital input 3 [13]
0x2631:042 (P400.42) Select parameter set (bit 1) Digital input 4 [14]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
0x4046 (P755.00) Acvaon of parameter set If the selecon is changed (disable required) [2]
t
t
t
t
t
t
t
t
t
t
t
1
2
41 3 3
RunDigital input 1 [11]
Select par. set (bit 0)
Enable inverter
Select par. set (bit 1)Digital input 4 [14]
Constant TRUE [1]
Digital input 3 [13]
Digital input 2 [12]
Mains voltage
Parameter set 4 active [111]
Parameter set 1 active [108]
Parameter set 3 active [110]
Parameter set 2 active [109]
Output signals
Status signals
Active parameter set
Load parameter set
Input signals
FunctionTrigger
The status signals can be assigned to digital outputs. 4Conguraon of digital outputs ^ 603
①
The "Load parameter set" funcon is ignored in this conguraon.
②
Change-over takes place by a status change of the selecon inputs.
③
If the inverter is enabled and the motor is started, a change-over is not possible.
Flexible I/O conguraon
Funcons for parameter change-over
Example 3: Acvaon if the selecon is changed (only if the inverter is disabled)
583