9.9.6 Data mapping
The process data are used to control the inverter.
The process data is transmied cyclically between the IO-Controller and the IO-Devices parc-
ipang at the PROFINET:
The available 27 network registers ("slots") serve to maximally exchange 16 process data
words (data types 8-bit or 16-bit) or 8 process data double words (data type 32-bit) for
each direcon.
Output data direcon: From IO-Controller to IO-Device.
Input data direcon: From IO-Device to IO-Controller.
Data mapping is used to dene which process data are exchanged cyclically between IO-Con-
troller andIO-Device.
Details
If the inverter is known in the PROFINET network as node and the IO-Controller connects
to the IO-Device for the rst me, the mapping objects are automacally transferred to
the IO device, i. e. to the inverter.
Internal mapping of the process output data is set in 0x24E0:001 ... 0x24E0:016.
Internal mapping of the process input data is set in 0x24E1:001 ... 0x24E1:016.
All subsequent changes in the objects 0x24E1 and 0x24E1 can cause PROFINET
alarms according to the deviaon of the automacally set conguraons.
Conguring the network
PROFINET
Data mapping
371