16.1.1 Keypad operang mode
Aer switching on the inverter, the keypad plugged in is in "Operang mode" aer a short
inialisaon phase.
16.1.1.1 Keypad status display
In the operang mode, the keypad displays informaon on the status of the inverter.
Keypad display Display Meaning
If the inverter is inhibited, the keypad shows "STOP":
S T O P
MAN AUTO SETLOC REM
VEL:FLEX:AIN1
If the inverter is enabled, the keypad shows the output
frequency of the inverter:
MAN AUTO SETLOC REM
HzVEL:RUN:FWD
O O O O 2 O O
•
In the process controller mode, instead of the output
frequency, the process controller setpoint is displayed.
•
The display can be congured in 0x2864 (P703.00).
•
The language for the keypad display is preset to "Eng-
lish". The language can be changed in 0x2863
(P705.00).
①
Acve control mode:
VEL Speed mode
PID Process controller mode
TRQ Torque mode
JOG Manual mode
②
Acve control source:
FLEX Flexible I/O conguraon
KPD Keypad
KPDF Keypad (complete control via keypad including setpoint selecon)
NET Network
③
Acve setpoint source:
AINx Analog input x
KPD Keypad
NET Network
FREQ Digital frequency
PRx Preset setpoint x
SEGx Segment x
MOP Motor potenometer
④
Current direcon of rotaon:
FWD Motor is rotang forwards
REV Motor is rotang backwards
⑤
Lower status line:
LOC Local keypad control acve.
REM Remote control via terminals, network, etc. acve.
MAN Manual setpoint selecon via keypad acve.
AUTO Automac setpoint selecon via terminals, network, etc. acve.
SET Blinking if one parameter seng has been changed but has not been
saved in the memory module with mains failure protecon.
Save sengs: Press keypad enter key longer than 3 s.
If an error is pending, the keypad shows the following
informaon:
MAN AUTO SETLOC REM
Warn.DC Bus UV
O 1 W 3 2 2 1
•
Faults (F) and trouble (T) are displayed connuously.
•
Warnings (W) are only displayed every 2 seconds for a
short me.
①
Error text
②
Error type:
F Fault
T Trouble
W Warning
③
Error code (hexadecimal)
4Error codes ^ 639
4Error handling ^ 139
4Error reset with keypad ^ 634
MAN AUTO SETLOC REM
AI1 fault
Restart Pending
O O F 7 O 8 1
Aer a disturbance, a restart is possible if the error condion is not acve anymore.
The keypad shows this by the "Restart Pending" note. The note is displayed in a 1-sec-
ond interval alternang with the error text.
4Automac restart ^ 484