Parameter Name / value range / [default seng] Info
0x23A9
(P517.00)
EtherNet/IP status
(EtherN/IP status)
Read only
From version 02.00
Display of the acve network status.
Related topics
4EtherNet/IP ^ 316
6.2.4.5 PROFINET diagnoscs
The following parameters serve to diagnose the PROFINET interface and the communicaon
via PROFINET.
Precondions
Control unit (CU) of the inverter is provided with PROFINET.
Parameter Name / value range / [default seng] Info
0x2382:001
(P511.01)
Acve PROFINET sengs: IP address
(PROFINET diag.: IP address)
Read only
From version 02.00
Display of the acve IP address.
0x2382:002
(P511.02)
Acve PROFINET sengs: Subnet
(PROFINET diag.: Subnet)
Read only
From version 02.00
Display of the acve subnet mask.
0x2382:003
(P511.03)
Acve PROFINET sengs: Gateway
(PROFINET diag.: Gateway)
Read only
From version 02.00
Display of the gateway address.
0x2382:004
(P511.04)
Acve PROFINET sengs: Staon name
(PROFINET diag.: Staon name)
Read only
From version 02.00
Display of the acve staon name.
0x2382:005
(P511.05)
Acve PROFINET sengs: MAC Address
(PROFINET diag.: MAC Address)
Read only
From version 02.00
Display of the acve MAC address.
0x2388
(P516.00)
PROFINET status
(PROFINET status)
Read only
From version 02.00
Bit coded display of the current Bus status.
Bit 0 Inialized Aer inialisaon, the network component waits for a communicaon
partner and the system power-up.
Bit 1 Online
Bit 2 Connected
Bit 3 IP address error The IP address is invalid. Valid IP addresses are dened according to RFC
3330.
Bit 4 Hardware fault
Bit 6 Watchdog elapsed PROFINET communicaon is connuously interrupted in the
"Data_Exchange" state, e.g. by cable break or failure of the IO Controller.
PROFINET communicaon changes to the "No_Data_Exchange" state.
When the watchdog monitoring me specied by the IO Controller has
elapsed, the response set in 0x2859:001 (P515.01) is triggered in the
inverter.
Bit 7 Protocol error
Bit 8 PROFINET stack ok
Bit 9 PROFINET stack not congured
Bit 10 Ethernet controller fault
Bit 11 UDP stack fault
Diagnoscs and fault eliminaon
Diagnoscs parameter
Network diagnoscs
126