14.16.2 Analog output 2
Sengs for analog input 2.
Precondions
Control Unit (CU) with applicaon I/O
Details
The analog output 2 is controlled with the signal selected in 0x263A:002 (P441.02).
The following sengs are possible for the analog output:
•
Denion of the signal range
①
•
Denion of the output range
②
AO2
0x263A:0010x263A 003:
0x263A 004:
X3
0x2DAB:001
V/mA
0x263A:002
0x2DAB:002
[V]
[mA]
Min
Max
Signal
Diagnosc parameters:
•
The current output voltage is displayed in 0x2DAB:002 (P113.02).
•
The actual output current is displayed in 0x2DAB:001 (P113.01).
For further details and conguraon examples, see chapter "Analog output 1". ^ 617
Parameter Name / value range / [default seng] Info
0x263A:001
(P441.01)
Analog output 2: Output range
(Analog output 2: AO2 outp. range)
•
Only available for applicaon I/O.
Denion of the output range.
0 Inhibited
1 0 ... 10 VDC
2 0 ... 5 VDC
3 2 ... 10 VDC
4 4 ... 20 mA
5 0 ... 20 mA
0x263A:002
(P441.02)
Analog output 2: Funcon
(Analog output 2: AO2 funcon)
•
Only available for applicaon I/O.
Selecon of the signal to be shown at analog output 2.
0 Not acve No output signal.
1 Output frequency Actual output frequency (resoluon: 0.1 Hz).
2 Frequency setpoint Actual frequency setpoint (resoluon: 0.1 Hz).
3 Analog input 1 Input signal of analog input 1 (resoluon: 0.1 %).
4 Analog input 2 Input signal of analog input 2 (resoluon: 0.1 %).
5 Motor current Actual motor current (resoluon: 0.1 A).
6 Output power Actual output power (resoluon: 0.001 kW).
7 Torque actual value Torque actual value (resoluon: 0.1 %).
•
100 % ≡ permissible maximum torque 0x6072 (P326.00)
10 Sequencer controlled (from version 03.00) Voltage value which has been set for the currently executed sequencer
segment (resoluon: 0.01 V).
4Sequencer ^ 504
20 NetWordIN3 Actual value of the NetWordIN3 data word (resoluon: 0.1 %).
4Further process data ^ 251
21 NetWordIN4 Actual value of the NetWordIN4 data word (resoluon: 0.1 %).
4Further process data ^ 251
201 Internal value (from version 05.00) Internal values of the manufacturer.
202 Internal value (from version 05.00)
203 Internal value (from version 05.00)
204 Internal value (from version 05.00)
205 Internal value (from version 05.00)
206 Internal value (from version 05.00)
Flexible I/O conguraon
Conguraon of analog outputs
Analog output 2
620