Parameter Name / value range / [default seng] Info
0x2C02:004
(P351.04)
Slip frequency
(Slip frequency)
Read only: x.x Hz
Display of the rated slip determined.
0x2C01:001 Motor parameters: Number of pole pairs
Read only
Display of the number of pole pairs calculated from the rated speed and
rated frequency.
0x2C01:004
(P320.04)
Motor parameters: Rated speed
(Motor parameters: Rated speed)
Device for 50-Hz mains: 50 ... [1450] ... 50000 rpm
Device for 60-Hz mains: 50 ... [1750] ... 50000 rpm
General motor data.
Carry out sengs as specied by motor nameplate data.
Note!
When you enter the motor nameplate data, take into account the phase
connecon implemented for the motor (star or delta connecon). Only
enter the data applying to the connecon type selected.
0x2C01:005
(P320.05)
Motor parameters: Rated frequency
(Motor parameters: Rated frequency)
Device for 50-Hz mains: 1.0 ... [50.0] ... 1000.0 Hz
Device for 60-Hz mains: 1.0 ... [60.0] ... 1000.0 Hz
Motor control
Opmisaon of motor control
Slip compensaon
189