Parameter Name / value range / [default seng] Info
101 Sequence acve (from version 03.00) Status signal of the "sequencer" funcon:
TRUE if the sequence is running and is currently not suspended.
4Sequencer ^ 504
102 Sequence suspended (from version 03.00) Status signal of the "sequencer" funcon:
TRUE if the sequence is currently suspended.
4Sequencer ^ 504
103 Sequence done (from version 03.00) Status signal of the "sequencer" funcon:
TRUE if the sequence is completed (nal segment has been passed
through).
4Sequencer ^ 504
104 Local control acve TRUE if local keypad control ("LOC") acve. Otherwise FALSE.
105 Remote control acve TRUE if remote control ("REM") via terminals, network, etc. acve. Oth-
erwise FALSE.
106 Manual setpoint selecon acve TRUE if manual setpoint selecon ("MAN") via keypad acve. Otherwise
FALSE.
Selecon of the trigger for the "Acvate keypad setpoint" funcon in
0x2631:016 (P400.16).
107 Automac setpoint selecon acve TRUE if automac setpoint selecon ("AUTO") via terminals, network,
etc. acve. Otherwise FALSE.
108 Parameter set 1 acve TRUE if parameter set 1 is loaded and acve. Otherwise FALSE.
109 Parameter set 2 acve TRUE if parameter set 2 is loaded and acve. Otherwise FALSE.
110 Parameter set 3 acve TRUE if parameter set 3 is loaded and acve. Otherwise FALSE.
111 Parameter set 4 acve TRUE if parameter set 4 is loaded and acve. Otherwise FALSE.
112 Parameter set load OK TRUE aer any parameter set has been loaded. Otherwise FALSE.
113 Parameter set load fail TRUE if any of the parameter sets could not be loaded. Otherwise FALSE.
115 Release holding brake Trigger signal for releasing the holding brake (TRUE = release holding
brake).
Note!
If this trigger is assigned to the relay or a digital output, the deceleraon
mes set for the respecve output are not eecve (are internally set to
"0"). Only the deceleraon me set in 0x2820:012 (P712.12) for closing
the holding brake inuences in this case the me-dependent behaviour
of the output.
4Holding brake control ^ 472
117 Motor phase failure TRUE if a motor phase failure has been detected. Otherwise FALSE.
4Motor phase failure detecon ^ 223
118 UPS operaon acve TRUE if UPS operaon is acve. Otherwise FALSE.
4UPS operaon ^ 490
155 Both STO channels not acve TRUE if safe inputs SIA and SIB = LOW (simultaneously). Otherwise
FALSE.
0x2635:001
(P421.01)
Inversion of digital outputs: Relay
(DO inversion: Relay inverted)
Relay inversion
0 Not inverted
1 Inverted
0x4018:003 Relay: Switch-o delay
0.000 ... [0.000] ... 65.535 s
Switch-o delay for the relay.
Note!
The set delay me is not eecve (internally set to "0") if the relay is
assigned to the trigger "Release holding brake [115]". Only the decelera-
on me set in 0x2820:012 (P712.12)for closing the holding brake inu-
ences the me-dependent behaviour of the relay.
0x4018:004 Relay: Switch-on delay
0.000 ... [0.000] ... 65.535 s
Switch-on delay for the relay.
Note!
The set delay me is not eecve (internally set to "0") if the relay is
assigned to the trigger "Release holding brake [115]". Only the decelera-
on me set in 0x2820:012 (P712.12)for closing the holding brake inu-
ences the me-dependent behaviour of the relay.
0x4018:005 Relay: Relay state
Read only
Display of the logic state of the relay.
0 FALSE
1 TRUE
Flexible I/O conguraon
Conguraon of digital outputs
Relay
606