Parameter Name / value range / [default seng] Info
101 Sequence acve (from version 03.00) Status signal of the "sequencer" funcon:
TRUE if the sequence is running and is currently not suspended.
4Sequencer ^ 504
102 Sequence suspended (from version 03.00) Status signal of the "sequencer" funcon:
TRUE if the sequence is currently suspended.
4Sequencer ^ 504
103 Sequence done (from version 03.00) Status signal of the "sequencer" funcon:
TRUE if the sequence is completed (nal segment has been passed
through).
4Sequencer ^ 504
104 Local control acve TRUE if local keypad control ("LOC") acve. Otherwise FALSE.
105 Remote control acve TRUE if remote control ("REM") via terminals, network, etc. acve. Oth-
erwise FALSE.
106 Manual setpoint selecon acve TRUE if manual setpoint selecon ("MAN") via keypad acve. Otherwise
FALSE.
•
Selecon of the trigger for the "Acvate keypad setpoint" funcon in
0x2631:016 (P400.16).
107 Automac setpoint selecon acve TRUE if automac setpoint selecon ("AUTO") via terminals, network,
etc. acve. Otherwise FALSE.
108 Parameter set 1 acve TRUE if parameter set 1 is loaded and acve. Otherwise FALSE.
109 Parameter set 2 acve TRUE if parameter set 2 is loaded and acve. Otherwise FALSE.
110 Parameter set 3 acve TRUE if parameter set 3 is loaded and acve. Otherwise FALSE.
111 Parameter set 4 acve TRUE if parameter set 4 is loaded and acve. Otherwise FALSE.
112 Parameter set load OK TRUE aer any parameter set has been loaded. Otherwise FALSE.
113 Parameter set load fail TRUE if any of the parameter sets could not be loaded. Otherwise FALSE.
115 Release holding brake Trigger signal for releasing the holding brake (TRUE = release holding
brake).
Note!
If this trigger is assigned to the relay or a digital output, the deceleraon
mes set for the respecve output are not eecve (are internally set to
"0"). Only the deceleraon me set in 0x2820:012 (P712.12) for closing
the holding brake inuences in this case the me-dependent behaviour
of the output.
4Holding brake control ^ 472
117 Motor phase failure TRUE if a motor phase failure has been detected. Otherwise FALSE.
4Motor phase failure detecon ^ 223
118 UPS operaon acve TRUE if UPS operaon is acve. Otherwise FALSE.
4UPS operaon ^ 490
155 Both STO channels not acve TRUE if safe inputs SIA and SIB = LOW (simultaneously). Otherwise
FALSE.
0x2635:001
(P421.01)
Inversion of digital outputs: Relay
(DO inversion: Relay inverted)
Relay inversion
0 Not inverted
1 Inverted
0x4018:003 Relay: Switch-o delay
0.000 ... [0.000] ... 65.535 s
Switch-o delay for the relay.
Note!
The set delay me is not eecve (internally set to "0") if the relay is
assigned to the trigger "Release holding brake [115]". Only the decelera-
on me set in 0x2820:012 (P712.12)for closing the holding brake inu-
ences the me-dependent behaviour of the relay.
0x4018:004 Relay: Switch-on delay
0.000 ... [0.000] ... 65.535 s
Switch-on delay for the relay.
Note!
The set delay me is not eecve (internally set to "0") if the relay is
assigned to the trigger "Release holding brake [115]". Only the decelera-
on me set in 0x2820:012 (P712.12)for closing the holding brake inu-
ences the me-dependent behaviour of the relay.
0x4018:005 Relay: Relay state
•
Read only
Display of the logic state of the relay.
0 FALSE
1 TRUE
Flexible I/O conguraon
Conguraon of digital outputs
Relay
606