Error code Error message Error type Congurable in
30338 0x7682 Memory module: invalid user data Fault -
30340 0x7684 Data not completely saved before switch-o Warning -
30342 0x7686 Internal communicaon error Fault -
30345 0x7689 Memory module: invalid OEM data Warning -
30346 0x768A Memory module: wrong type Fault -
30352 0x7690 EPM rmware version incompable Fault -
30353 0x7691 EPM data: rmware type incompable Fault -
30354 0x7692 EPM data: new rmware type detected Fault -
30355 0x7693 EPM data: PU size incompable Fault -
30356 0x7694 EPM data: new PU size detected Fault -
30357 0x7695 Invalid conguraon of parameter change-over Warning -
30358 0x7696 EPM data: unknown parameter found Info -
30359 0x7697 Changed parameters lost Fault -
33042 0x8112 Network: meout explicit message Warning 0x2859:006 (P515.06)
33044 0x8114 Network: overall communicaon meout Warning See details for 33044
33045 0x8115 Time-out (PZÜ) No response 0x2552:004 (P595.04)
33046 0x8116 Modbus TCP master me-out Fault 0x2859:008 (P515.08)
33047 0x8117 Modbus TCP Keep Alive me-out Fault 0x2859:009 (P515.09)
33154 0x8182 CAN: bus o Trouble 0x2857:010
33155 0x8183 CAN: warning Warning 0x2857:011
33156 0x8184 CAN: heartbeat me-out consumer 1 Fault 0x2857:005
33157 0x8185 CAN: heartbeat me-out consumer 2 Fault 0x2857:006
33158 0x8186 CAN: heartbeat me-out consumer 3 Fault 0x2857:007
33159 0x8187 CAN: heartbeat me-out consumer 4 Fault 0x2857:008
33168 0x8190 Network: watchdog meout Trouble See details for 33168
33169 0x8191 Network: disrupon of cyclic data exchange No response 0x2859:002 (P515.02)
33170 0x8192 Network: inialisaon error Trouble See details for 33170
33171 0x8193 Network: invalid cyclic process data Trouble See details for 33171
33185 0x81A1 Modbus: network me-out Fault 0x2858:001 (P515.01)
33186 0x81A2 Modbus: incorrect request by master Warning -
33200 0x81B0 iCIF connecon lost Fault -
33414 0x8286 Network: PDO mapping error Trouble See details for 33414
33425 0x8291 CAN: RPDO1 me-out Fault 0x2857:001
33426 0x8292 CAN: RPDO2 me-out Fault 0x2857:002
33427 0x8293 CAN: RPDO3 me-out Fault 0x2857:003
33553 0x8311 Torque limit reached No response 0x2D67:001 (P329.01)
36992 0x9080 Keypad removed Fault -
65282 0xFF02 Brake resistor: overload warning Fault 0x2550:011 (P707.11)
65285 0xFF05 Safe Torque O error Fault -
65286 0xFF06 Motor overspeed Fault 0x2D44:002 (P350.02)
65289 0xFF09 Motor phase missing No response 0x2D45:001 (P310.01)
65290 0xFF0A Phase U motor phase failure No response 0x2D45:001 (P310.01)
65291 0xFF0B Motor phase failure phase V No response 0x2D45:001 (P310.01)
65292 0xFF0C Motor phase failure phase W No response 0x2D45:001 (P310.01)
65305 0xFF19 Motor parameter idencaon error Fault -
65334 0xFF36 Brake resistor: overload warning Warning 0x2550:010 (P707.10)
65335 0xFF37 Automac start disabled Fault -
65366 0xFF56 Maximum motor frequency reached Warning -
65413 0xFF85 Keypad full control acve Warning -
Appendix
Error codes
640

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55 Series and is the answer not in the manual?

Lenze i55 Series Specifications

General IconGeneral
BrandLenze
Modeli55 Series
CategoryInverter
LanguageEnglish

Related product manuals