9 Visualization
Maschinenfabrik Reinhausen GmbH 2020128 4453918/14 ENETOS
®
TD
Min. fan run time after error
You can use this parameter to set how long the fans are to continue running
if an error occurs in the cooling system control. The fans run at full power for
this duration.
Minimum fan speed
You can use this parameter to set the minimum fan speed.
Maximum fan speed
You can use this parameter to set the maximum fan speed.
Upper top-oil temperature threshold
You can use this parameter to set the top-oil temperature at which the fans
are to run at maximum speed.
Lower top-oil temperature threshold
You can use this parameter to set the top-oil temperature at which the fans
are to run at minimum speed.
Upper load factor threshold
You can use this parameter to set the load factor at which the fans are to run
at maximum speed.
Lower load factor threshold
You can use this parameter to set the load factor at which the fans are to run
at minimum speed.
9.10.8 Displaying status of cooling stages
You can display the status of the cooling stages. The following information is
available to you for every cooling stage:
Status
Gray: Cooling stage inactive
Blue: Cooling stage active
Yellow, red: Event message
Number of starts
Operating time
Parameter set
Delay time
Hysteresis
Switch-on threshold