9 Visualization
Maschinenfabrik Reinhausen GmbH 2020188 4453918/14 ENETOS
®
TD
Note that the parameters "Error if no communication" and "Behavior if no
communication" have no function in the circulating reactive current mini-
mization without CAN communication parallel operation method.
9.21.2 Configuring parallel operation
In the Parallel operation menu item, you can set the parameters needed for
parallel transformer operation.
Settings
Parameters
Name Value
Activating parallel operation On
Parallel operation method Master
CAN bus address 1
Circulating reactive current sens... 0.0%
Circulating reactive current bloc... 20.0%
Desired power factor 0.9
Desired load stress type Inductive
Master/follower current blocking Off
Maximum tap difference 1
Master/follower switching charact... Sequential
Error if no communication present No error
Behavior if no communication pres... Independent regulation
Parallel operation error delay ti... 10s
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin 03.02.2020 08:09
Figure127: Parallel operation
1. Go to Settings > Parameters > Grid > Parallel operation.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the Accept button to save the modified parameter.
Activating parallel operation
You can use this parameter to activate parallel operation.