Bulletin 284G Programmable Parameters for Sensorless Vector Controllers 4-25
Basic Program Group
Stp Logic Status
When Parameter 138 (Speed Reference) is set to 6 Stp Logic, this parameter will
display the current step of step logic as defined by Parameters 240…247 (Stp
Logic X).
Parameter Number 128
Access Rule GET
Data Type UINT
Group Display Group
Units 1
Minimum Value 0
Maximum Value 8
Default Value Read Only
Torque Current
The current value of the motor torque current.
Parameter Number 129
Related Parameters
Access Rule GET
Data Type UINT
Group Display Group
Units 0.01
Minimum Value 0.00
Maximum Value Drive Rated Amps x 2
Default Value Read Only
Motor NP Volts
Set to the motor name plate rated volts.
Parameter Number 131
Related Parameters 104, 184, 185…187
Access Rule GET/SET
Data Type UINT
Group Basic Program
Units 1V AC
Minimum Value 20
Maximum Value 240V, 460V, or 600V AC
Default Value Based on Drive Rating
Motor NP Hertz
Set to the motor nameplate rated frequency.
Parameter Number 132
Related Parameters 184, 185…187, and 190
Access Rule GET/SET
Data Type UINT
Group Basic Program
Units 1 Hz
Minimum Value 15
Maximum Value 400
Default Value 60 Hz
Stop drive before changing this parameter.
Stop drive before changing this parameter.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation ArmorStart Bulletin 280G and is the answer not in the manual?

Rockwell Automation ArmorStart Bulletin 280G Specifications

General IconGeneral
BrandRockwell Automation
ModelArmorStart Bulletin 280G
CategoryController
LanguageEnglish

Related product manuals