Bulletin 280G/281G Programmable Parameters 3-23
Starter Display
Zone #4 KEY
When the “Security Enable” bit
for zone 4 is enabled, this value
must match the value of the
Device Value Key parameter in
the device whose data is being
consumed for zone 4
Parameter Number 97
Access Rule GET/SET
Data Type UINT
Group ZIP Parameters
Units —
MinimumValue 0
Maximum Value 65535
Default Value 0
Device Value Key
This value is produced in the last
2 bytes of data when one of the
ZIP assemblies is chosen for data
production.
Parameter Number 98
Access Rule GET/SET
Data Type UINT
Group ZIP Parameters
Units —
MinimumValue 0
Maximum Value 65535
Default Value 0
Zone Ctrl Enable
Global enable for ZIP peer-to-
peer messaging. This parameter
must be disabled before any
changes to the ZIP configuration
for the device can be made.
0=Disable
1=Enable
Parameter Number 99
Access Rule GET/SET
Data Type BOOL
Group ZIP Parameters
Units —
MinimumValue 0
Maximum Value 1
Default Value 0
Phase A Current
This parameter provides the
current of Phase A measured n
increments of 1/10
th
of an
ampere
Parameter Number 101
Access Rule GET/SET
Data Type INT
Group Starter Display
Units xx.x Amps
Minimum Value 0
Maximum Value 32767
Default Value 0
Phase B Current
This parameter provides the
current of Phase B measured in
increments of 1/10
th
of an
ampere
Parameter Number 102
Access Rule GET/SET
Data Type INT
Group Starter Display
Units xx.x Amps
Minimum Value 0
Maximum Value 32767
Default Value 0