Bulletin 280G/281G CIP Information B-7
Table B.19 Instance 185 This is a “Read Only” Status Assembly
Table B.20 Instance 186 This is a “Read Only” Status Assembly
Table B.21 Instance 187 This is a “Read/Write” Assembly
Table B.22 Instance 189 This is a “Read-Only” Assembly
Standard Distributed Motor
Controller I/O Assemblies
Standard Distributed Motor Controller IO Assemblies are available
on all Starter Types.
Standard Distributed Motor Controller Output (Consumed)
Assemblies
Table B.23 Instance 3 is the required output (consumed) assembly defined in
the DeviceNet Motor Starter Profile
Instance 185 — Starter Status
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0At Ref —
Net Ctl
Status
Ready
Running
Rev
Running
Fwd
Warning Tripped
1— —140M On
HOA
Stat.
Keypad
Hand
———
Instance 186 — DeviceNet Status
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 — — — I/O Idle I/O Flt Exp Flt I/O Cnxn Exp Cnxn
1 ZIP FLT ZIP4 CNX ZIP3 FLT ZIP2 CNX ZIP2 FLT ZIP2 CNX ZIP1 FLT ZIP1 CNX
Instance 187 — Starter Control Bits
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
User Out
B
User Out
A
———
Fault
Reset
Run Rev Run Fwd
1————————
Instance 189 — Warning Status Bits
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0—
IO
Warning
Control
Power
Warning
——
PL
Warning
——
1 — — HW Warn — — — DN Warn PI Warn
Instance 3 — ODVA Starter
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0———————Run Fwd