3-24 Bulletin 280G/281G Programmable Parameters
Starter Setup
Table 3.2 FLA Setting Ranges and Default Values (with indicated setting
precision)
Phase C Current
This parameter provides the
current of Phase C measured in
increments of 1/10
th
of an
ampere
Parameter Number 103
Access Rule GET/SET
Data Type INT
Group Starter Display
Units xx.x Amps
Minimum Value 0
Maximum Value 32767
Default Value 0
Average Current
This parameter provides the
average current measured in
increments of 1/10
th
of an
ampere
Parameter Number 104
Access Rule GET/SET
Data Type INT
Group Starter Display
Units xx.x Amps
Minimum Value 0
Maximum Value 32767
Default Value 0
% Therm Utilized
This parameter displays the
% Thermal Capacity used
Parameter Number 105
Access Rule GET/SET
Data Type USINT
Group Starter Display
Units % FLA
Minimum Value 0
Maximum Value 100
Default Value 0
FLA Setting
The motor’s full load current
rating is programmed in this
parameter
Parameter Number 106
Access Rule GET/SET
Data Type INT
Group Starter Setup
Units xx.x Amps
Minimum Value See Table 3.2
Maximum Value See Table 3.2
Default Value See Table 3.2
FLA Current Range (A)
Default Value
Minimum Value Maximum Value
0.5 2.5 0.5
1.1 5.5 1.1
3.2 16.0 3.2