112 ACS550-02/U2 User’s Manual
Application macros
Macro default values for parameters
Parameter default values are listed in section Complete parameter list on page 115.
Changing from the default macro (ABB Standard), that is, editing the value of
parameter 9902, changes the parameter default values as defined in the following
tables.
Note: There are two sets of values because the defaults are configured for 50 Hz/
IEC compliance (ACS550-02) and 60 Hz/NEMA compliance (ACS550-U2).
ACS550-02
Parameter
ABB
Standard
3-wire
Alternate
Motor
Potentiometer
Hand-auto
PID Control
PFC Control
Torque
Control
9902 APPLIC MACRO 12345678
9904
MOTOR CTRL MODE 31111132
1001
EXT1 COMMANDS 24922112
1002
EXT2 COMMANDS 00007662
1003
DIRECTION 33333113
1102
EXT1/EXT2 SEL 00003233
1103
REF1 SELECT 111121111
1106
REF2 SELECT 2222219192
1201
CONST SPEED SEL 910950904
1304
MINIMUM AI2 0 0 0 020202020
1401
RELAY OUTPUT 1 11111121
1402
RELAY OUTPUT 2 22222232
1403
RELAY OUTPUT 3 333333313
1501
AO1 CONTENT SEL 103 102 102 102 102 102 103 102
1503
AO1 CONTENT MAX 50 50 50 50 50 50 52 50
1507
AO2 CONTENT SEL 104 104 104 104 104 104 130 104
1510
MINIMUM AO2 00000040
1601
RUN ENABLE 00664526
2008
MAXIMUM FREQ 50 50 50 50 50 50 52 50
2201
ACC/DEC 1/2 SEL 50500005
3201
SUPERV 1 PARAM 103 102 102 102 102 102 103 102
3401
SIGNAL1 PARAM 103 102 102 102 102 102 103 102
4001
GAIN 10 10 10 10 10 10 25 10
4002
INTEGRATION TIME 60 60 60 60 60 60 3 60
4101
GAIN 1111112,51
4102
INTEGRATION TIME 60 60 60 60 60 60 3 60
8123
PFC ENABLE 00000010