88 ACS550-02/U2 User’s Manual
Control panels
Parameter Backup mode
The Parameter Backup mode is used to export parameters from one drive to another
or to make a backup of the drive parameters. Uploading to the panel stores all drive
parameters, including up to two user sets, to the Assistant Control Panel. The full
set, partial parameter set (application) and user sets can then be downloaded from
the control panel to another drive or the same drive.
The control panel memory is non-volatile and does not depend on the panel battery.
In the Parameter Backup mode, you can:
copy all parameters from the drive to the control panel (UPLOAD TO PANEL).
This includes all defined user sets of parameters and internal (not adjustable by
the user) parameters such as those created by the ID Run.
view the information about the backup stored to the control panel with UPLOAD
TO PANEL (BACKUP INFO). This includes e.g. the type and rating of the drive
where the backup was made. It is useful to check this information when you are
going to copy the parameters to another drive with DOWNLOAD FULL SET to
ensure that the drives match.
restore the full parameter set from the control panel to the drive (DOWNLOAD
FULL SET). This writes all parameters, including the internal non-user-adjustable
motor parameters, to the drive. It does not include the user sets of parameters.
Note: Only use this function to restore a drive from a backup or to transfer
parameters to systems that are identical to the original system.
copy a partial parameter set (part of the full set) from the control panel to a drive
(DOWNLOAD APPLICATION). The partial set does not include user sets, internal
motor parameters, parameters 99059909, 1605, 1607, 5201, nor any Group
51: EXT COMM MODULE and Group 53: EFB PROTOCOL parameters.
The source and target drives and their motor sizes do not need to be the same.
copy USER S1 parameters from the control panel to the drive (DOWNLOAD
USER SET1). A user set includes Group 99: START-UP DATA parameters and
the internal motor parameters.
The function is only shown on the menu when User Set 1 has been first saved
using parameter 9902
APPLIC MACRO (see section User parameter sets on page
111) and then uploaded to the control panel with UPLOAD TO PANEL.
copy USER S2 parameters from the control panel to the drive (DOWNLOAD
USER SET2). As DOWNLOAD USER SET1 above.
start, stop, change the direction and switch between local and remote control.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS550-02 and is the answer not in the manual?

ABB ACS550-02 Specifications

General IconGeneral
BrandABB
ModelACS550-02
CategoryDC Drives
LanguageEnglish

Related product manuals