ACS550-02/U2 User’s Manual 99
Control panels
Copy mode
The Basic Control Panel can store a full set of drive parameters and up to two user
sets of drive parameters to the control panel. The control panel memory is non-
volatile.
In the Copy mode, you can:
• copy all parameters from the drive to the control panel (uL – Upload). This
includes all defined user sets of parameters and internal (not adjustable by the
user) parameters such as those created by the ID Run.
• restore the full parameter set from the control panel to the drive (dL A – Download
All). This writes all parameters, including the internal non-user-adjustable motor
parameters, to the drive. It does not include the user sets of parameters.
Note: Only use this function to restore a drive, or to transfer parameters to
systems that are identical to the original system.
• copy a partial parameter set from the control panel to a drive (dL P – Download
Partial). The partial set does not include user sets, internal motor parameters,
parameters 9905…9909, 1605, 1607, 5201, nor any Group 51: EXT COMM
MODULE and Group 53: EFB PROTOCOL parameters.
The source and target drives and their motor sizes do not need to be the same.
• copy USER S1 parameters from the control panel to the drive (dL u1 – Download
User Set 1). A user set includes Group 99: START-UP DATA parameters and the
internal motor parameters.
The function is only shown on the menu when User Set 1 has been first saved
using parameter 9902
APPLIC MACRO (see section User parameter sets on page
111) and then uploaded to panel.
• copy USER S2 parameters from the control panel to the drive (dL u2 – Download
User Set 2). As dL u1 – Download User Set 1 above.
• start, stop, change the direction and switch between local and remote control.