Name Type Description
QC5REL BOOLEAN Switching of QC5 is allowed
QC5ITL BOOLEAN Switching of QC5 is forbidden
QB2OPTR BOOLEAN QB2 is in open position
QB2CLTR BOOLEAN QB2 is in closed position
VPQB2TR BOOLEAN Switch status of QB2 is valid (open or closed)
Table 256: DB_LINE Output signals
Name Type Description
QB9REL BOOLEAN Switching of QB9 is allowed
QB9ITL BOOLEAN Switching of QB9 is forbidden
QC3REL BOOLEAN Switching of QC3 is allowed
QC3ITL BOOLEAN Switching of QC3 is forbidden
QC9REL BOOLEAN Switching of QC9 is allowed
QC9ITL BOOLEAN Switching of QC9 is forbidden
12.3.8.6 Settings
The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).
12.3.9 Interlocking for line bay ABC_LINE
12.3.9.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for line bay ABC_LINE - 3
12.3.9.2 Functionality
The interlocking for line bay (ABC_LINE) function is used for a line connected to a
double busbar arrangement with a transfer busbar according to figure 197. The
function can also be used for a double busbar arrangement without transfer busbar or
a single busbar arrangement with/without transfer busbar.
Section 12 1MRK 502 048-UEN A
Control
394