Name Values (Range) Unit Step Default Description
ILMax 0 - 500000 A 1 1300 Maximum value
ILRepTyp Cyclic
Dead band
Int deadband
-
- Dead band Reporting type
ILAngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Table 353: CMMXU Non group settings (advanced)
Name Values (Range) Unit Step Default Description
ILZeroDb 0 - 100000 m% 1 500 Zero point clamping
ILHiHiLim 0 - 500000 A 1 1200 High High limit (physical value)
ILHiLim 0 - 500000 A 1 1100 High limit (physical value)
ILLowLim 0 - 500000 A 1 0 Low limit (physical value)
ILLowLowLim 0 - 500000 A 1 0 Low Low limit (physical value)
ILMin 0 - 500000 A 1 0 Minimum value
ILLimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at 5%
of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
30% of Ir
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at
100% of Ir
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir
14.1.3.5 Monitored data
Table 354: CMMXU Monitored data
Name
Type Values (Range) Unit Description
IL1 REAL - A IL1 Amplitude
IL1ANGL REAL - deg IL1 Angle
IL2 REAL - A IL2 Amplitude
IL2ANGL REAL - deg IL2 Angle
IL3 REAL - A IL3 Amplitude
IL3ANGL REAL - deg IL3 Angle
1MRK 502 048-UEN A Section 14
Monitoring
479
Technical manual