Table 315: TIMERSET Output signals
Name Type Description
ON BOOLEAN Output signal, pick-up delayed
OFF BOOLEAN Output signal, drop-out delayed
Settings
Table 316: TIMERSET Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
t 0.000 - 90000.000 s 0.001 0.000 Delay for settable timer n
13.3.1.9 AND function block
Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
AND function block AND - -
Functionality
The AND function is used to form general combinatory expressions with boolean
variables. The AND function block has four inputs and two outputs.
Default value on all four inputs are logical 1 which makes it possible for the user to just
use the required number of inputs and leave the rest un-connected. The output OUT
has a default value 0 initially, which suppresses one cycle pulse if the function has
been put in the wrong execution order.
Function block
AND
INPUT1
INPUT2
INPUT3
INPUT4
OUT
NOUT
IEC09000289-1-en.vsd
IEC09000289 V1 EN
Figure 225: AND function block
Section 13 1MRK 502 048-UEN A
Logic
448
Technical manual

Table of Contents

Other manuals for ABB REG650

Questions and Answers:

ABB REG650 Specifications

General IconGeneral
ModelREG650
ManufacturerABB
Product TypeProtection Relay
Current Input1 A / 5 A
Frequency50 / 60 Hz
Frequency Rating50 / 60 Hz
Communication ProtocolsIEC 61850, Modbus, DNP3, IEC 60870-5-103
MountingPanel Mount
TypeProtection Relay
Current Rating1 A / 5 A
Protection FunctionsOvercurrent, Earth Fault
DisplayLCD Display
HousingMetal case
InputsBinary inputs, Analog inputs
OutputsBinary outputs
EnclosureIP20

Related product manuals