activated outputs OUTx where 1≤x≤16. The values represented by the different OUTx
are according to Table 340. When an OUTx is not activated, its value is 0.
The IB16FCVB function is designed for receiving the integer input from a station
computer - for example, over IEC 61850. If the BLOCK input is activated, it will
freeze the logical outputs at the last value.
Table 340: Outputs and their values when activated
Name of OUTx Type Description Value when
activated
Value when
deactivated
OUT1 BOOLEAN Output 1 1 0
OUT2 BOOLEAN Output 2 2 0
OUT3 BOOLEAN Output 3 4 0
OUT4 BOOLEAN Output 4 8 0
OUT5 BOOLEAN Output 5 16 0
OUT6 BOOLEAN Output 6 32 0
OUT7 BOOLEAN Output 7 64 0
OUT8 BOOLEAN Output 8 128 0
OUT9 BOOLEAN Output 9 256 0
OUT10 BOOLEAN Output 10 512 0
OUT11 BOOLEAN Output 11 1024 0
OUT12 BOOLEAN Output 12 2048 0
OUT13 BOOLEAN Output 13 4096 0
OUT14 BOOLEAN Output 14 8192 0
OUT15 BOOLEAN Output 15 16384 0
OUT16 BOOLEAN Output 16 32768 0
The sum of the numbers in column “Value when activated” when all OUTx (1≤x≤16)
are active equals 65535. This is the highest integer that can be converted to boolean by
the IB16FCVB function block.
The operator position input (PSTO) determines the operator place. The integer
number that is communicated to the IB16FCVB can only be written to the block while
the PSTO is in position “Remote”. If PSTO is in position ”Off” or ”Local”, then no
changes are applied to the outputs.
13.9 Elapsed time integrator with limit transgression and
overflow supervision TEIGGIO
13.9.1 Identification
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2 device
number
Elapsed time integrator TEIGGIO - -
1MRK 502 048-UEN A Section 13
Logic
465
Technical manual