Predened Modbus status registers
These registers are only provided with read access.
The cross-reference in column 2 leads to the detailed parameter descripon.
Modbus registers Permanently assigned parameter
Address Name
42001 0x400C:001 (P593.01) AC Drive status word
42002 0x400C:006 (P593.06) Frequency (0.01)
42003 0x603F (P150.00) Error code
42004 0x400C:005 (P593.05) Drive status
42005 0x2D89 (P106.00) Motor voltage
42006 0x2D88 (P104.00) Motor current
42007 0x6078 (P103.00) Current actual value
42008 0x2DA2:002 (P108.02) Apparent power
(42008 = High Word, 42009 = Low Word)
42009
42010 0x2D84:001 (P117.01) Heatsink temperature
42011 0x2D87 (P105.00) DC-bus voltage
42012 0x60FD (P118.00) Digital inputs (only bit 16 ... bit 31)
42013 0x6077 (P107.00) Torque actual value
42014 ... 42021 - Reserved
Variable mapping
Via 0x23BB:001 ... 0x23BB:024 (P530.01 ... 24), 24 registers can be mapped to parameters
of the inverter.
Format: 0xiiiiss00 (iiii = index, ss = subindex)
The display of the internal Modbus register numbers in 0x23BC:001 ... 0x23BC:024
(P531.01 ... 24) is generated automacally. Since 32-bit parameters require two registers,
there is no 1:1 assignment.
For the mappable registers, a CRC (Cyclic Redundancy Check) is executed. The checksum
determined is displayed in 0x23BD (P532.00). The user can read this "validaon code" and
use it for comparison in the Modbus master. In this way it can be checked whether the
inverter currently queried is congured correctly for the respecve applicaon.
Parameter Name / value range / [default seng] Info
0x23BB:001 ...
0x23BB:024
(P530.01 ... 24)
Modbus TCP/IP parameter mapping: Parameter 1 ...
Parameter 24
(MBTCP param.mapp: Parameter 1 ... Parameter 24)
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
Mapping entries for Modbus register 40103 ... 40149.
Format: 0xiiiiss00 (iiii = index, ss = subindex)
0x23BC:001 ...
0x23BC:024
(P531.01 ... 24)
Register assignment: Register 1 ... Register 24
(Register assignm: Register 1 ... Register 24)
Read only
Display of the internal Modbus register number starng from which the
parameter mapped in 0x23BB:001 ... 0x23BB:024 (P530.01 ... 24) is
stored.
For the rst parameter mapped, always 2500.
From the second parameter mapped, 2500 + oset. The oset results
from the data types of the previously mapped parameters.
0x23BD
(P532.00)
Vericaon code
(Vericat. code)
Read only
From version 04.00
Conguring the network
Modbus TCP
Data mapping
361

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55 Series and is the answer not in the manual?

Lenze i55 Series Specifications

General IconGeneral
BrandLenze
Modeli55 Series
CategoryInverter
LanguageEnglish

Related product manuals