Parameter Name / value range / [default seng] Info
17 Digital input 7 State of X3/DI7, taking an inversion set in 0x2632:007 (P411.07) into
consideraon.
Digital input 7 is only available in the Control Unit (CU) with applicaon
I/O.
30 NetWordIN1 - bit 12 State of NetWordIN1/bit 12 ... 15.
Display of NetWordIN1 in 0x4008:001 (P590.01).
For implemenng an individual control word format, NetWordIN1 can
be mapped to a process data input word.
31 NetWordIN1 - bit 13
32 NetWordIN1 - bit 14
33 NetWordIN1 - bit 15
34 NetWordIN2 - bit 0 State of NetWordIN2/bit 0 ... bit 15.
Display of NetWordIN2 in 0x4008:002 (P590.02).
For controlling the digital outputs via network, NetWordIN2 can be
mapped to a process data input word.
35 NetWordIN2 - bit 1
36 NetWordIN2 - bit 2
37 NetWordIN2 - bit 3
38 NetWordIN2 - bit 4
39 NetWordIN2 - bit 5
40 NetWordIN2 - bit 6
41 NetWordIN2 - bit 7
42 NetWordIN2 - bit 8
43 NetWordIN2 - bit 9
44 NetWordIN2 - bit 10
45 NetWordIN2 - bit 11
46 NetWordIN2 - bit 12
47 NetWordIN2 - bit 13
48 NetWordIN2 - bit 14
49 NetWordIN2 - bit 15
50 Running TRUE if inverter and start are enabled and output frequency > 0.2 Hz.
Otherwise FALSE.
51 Ready for operaon TRUE if inverter is ready for operaon (no error acve, no STO acve and
DC-bus voltage ok). Otherwise FALSE.
52 Operaon enabled TRUE if inverter and start are enabled. Otherwise FALSE.
53 Stop acve TRUE if inverter is enabled and motor is not started and output fre-
quency = 0.
54 Quick stop acve TRUE if quick stop is acve. Otherwise FALSE.
55 Safe torque o (STO) acve TRUE if the integrated safety system has triggered the "Safe torque o
(STO)" funcon. Otherwise FALSE.
4Safe torque o (STO) ^ 523
56 Error acve TRUE if error is acve. Otherwise FALSE.
57 Error (non-reseable) acve TRUE if non-reseable error is acve. Otherwise FALSE.
58 Device warning acve TRUE if warning is acve. Otherwise FALSE.
A warning has no impact on the operang status of the inverter.
A warning is reset automacally if the cause has been eliminated.
59 Device trouble acve TRUE if a fault is acve. Otherwise FALSE.
In the event of a fault, the motor is brought to a standsll with the
quick stop ramp. The inverter is then disabled.
Excepon: In case of a serious fault, the inverter is disabled immedi-
ately. The motor becomes torqueless (coasts).
The error state will be le automacally if the error condion is not
acve anymore.
The restart behaviour aer trouble can be congured. 4Automac
restart ^ 484
60 Heatsink temperature warning acve TRUE if current heatsink temperature > warning threshold for tempera-
ture monitoring. Otherwise FALSE.
Display of the current heatsink temperature in 0x2D84:001 (P117.01).
Seng of the warning threshold in 0x2D84:002.
65 Motor PTC error acve TRUE if an error of the motor PTC has been detected. Otherwise FALSE.
The trigger is set irrespecve of the response set in 0x2D49:002
(P309.02) when the motor temperature monitoring is triggered.
4Motor temperature monitoring ^ 219
66 Flying restart circuit acve TRUE if ying restart circuit acve is acve. Otherwise FALSE.
4Flying restart circuit ^ 481
Flexible I/O conguraon
Conguraon of digital outputs
Relay
604

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55 Series and is the answer not in the manual?

Lenze i55 Series Specifications

General IconGeneral
BrandLenze
Modeli55 Series
CategoryInverter
LanguageEnglish

Related product manuals