Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
234 Manual, 09.2018, A5E36758446-5-76
1-6 9 Channel8 Utarget
see data "Channel 1"
Channel8 Ilimit
[10 mA]
Channel8
Output data SITOP UPS8600
1-6 1 Maximum charging
power
Maximum charging power 0 (Off), 1 (Low), 2
(High)
Unsigned8
Data block active Indicator: Data block contains valid
0 = false, >0 = true
Unsigned8
Operating states SITOP PSU8600
Operating state of the power supply system (device operating state)
Power supply system is shut down.
1 = ErrorOff The power supply system was automatically switched off due to operation under impermis-
sible operating conditions.
2 = ReadyForRestart After an automatic shutdown due to a fault, the power supply system can be reactivated by
switching off and switching on the supply voltage.
The power supply system is starting up, all outputs are still switched off.
The power supply system is in normal operation.
5 = Phasefail Phase failure of the supply voltage detected. The power supply system can continue to
operate in the normal mode without any restrictions for a limited period of time.
6 = SystemOverload (IP) System overload within the permissible overload profile detected. The power supply system
continues to operate in normal mode.
7 = SystemOverload (OP) System overload outside the permissible overload profile detected. The power supply sys-
tem can only operate with restrictions.
8 = SystemOverload (PL) Very high, transient peak load detected. The power supply system is in normal operation.
Primary supply voltage has failed. The power supply system is in buffer mode.
10 = SystemOverload (IP)
System overload within the permissible overload profile detected. The power supply system
continues to operate in buffer mode.
11 = SystemOverload (OP)
System overload outside the permissible overload profile detected. The power supply sys-
tem can only operate with restrictions.
12 = SystemOverload (PL)
Very high, transient peak load detected. The power supply system is in buffer mode.