Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
344 Manual, 09.2018, A5E36758446-5-76
Parameters not described otherwise, in alphabetical order:
Display name
Data type
Definition
Description
DeviceManual String PropertyType Address (path in the file system or
URL/web address) of the operating
instructions for the unit.
HardwareRevision String PropertyType Hardware revision of the device
Manufacturer LocalizedText PropertyType Name of the company that manu-
factured the device
Model
LocalizedText
PropertyType
Model
ModuleCapacitySetpoint
Integer
AnalogItemType
Capacity of the batteries
ModuleEndOfChargeVoltageSet-
point
Float AnalogItemType End of charge voltage at 20°C
ModuleEndOfDischargeVoltage
Setpoint
Float AnalogItemType Discharge threshold at which buffer
mode is stopped.
ModuleMaxChargeCurrentSetpoint
Float
AnalogItemType
Maximum battery charging current
ModuleOperatingHours
Integer
AnalogItemType
Total operating time
ModuleOperatingState Enumeration MultiStateDiscrete-
Type
Battery status
ModuleOperatingTemperatureSet-
point
Float AnalogItemType Expected battery operating tem-
perature
ModuleStartOfPreserveVoltage
Setpoint
Float AnalogItemType Threshold at which the normal
charging of the batteries switches
over to pure trickle charging (short-
term recharging)
ModuleStateLed Object Sitop_8600_LedType Actual state of the LED display
"O.K."
ModuleStateOfHealth Integer AnalogItemType State of health of the battery mod-
ule
ModuleTempCoefficientSetpoint Integer AnalogItemType Temperature coefficient of the
charging current for battery charg-
ing (in 1 mV/K)
ModuleTemperature
Integer
AnalogItemType
Battery temperature
ModuleTypeSetpoint Enumeration MultiStateDiscrete-
Type
Battery type
SlotId
UInt16
PropertyType
Battery subslot number
7.8.6.20
User management
Display name
Data type
Definition
Description
AddUser
Method
-
Add new user
ChangeUserPassword
Method
-
Change password
DeleteUser
Method
-
Delete user
UsermanagementUser1 …
UsermanagementUser16
Object SitopUserType

Table of Contents

Other manuals for Siemens SITOP PSU8600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SITOP PSU8600 and is the answer not in the manual?

Siemens SITOP PSU8600 Specifications

General IconGeneral
BrandSiemens
ModelSITOP PSU8600
CategoryPower Supply
LanguageEnglish

Related product manuals