Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
321
7.8.6.5
Buffering
Display name
Data type
Definition
Description
BufferDeadtimeBuffering
ModeAlarmSetpoint
UInt32 AnalogItemType Dead time for buffering mode alarm
BufferDisableSetpoint Boolean PropertyType Deactivates the buffering if set to
TRUE.
BufferDurationShorttimeInterrup-
tionSetpoint
UInt32 AnalogItemType Duration of short-time interruption
BufferLonglifeOperationEnableSet-
point
Boolean PropertyType LONGLIFE operating mode acti-
vated
BufferReadyThresholdSetpoint Byte AnalogItemType Threshold value for sufficient buffer
readiness
BufferShorttimeInterruptionEna-
bleSetpoint
Boolean PropertyType Short-time interruption at output 1
is enabled
BufferWaittimeShorttimeInterrup-
tionSetpoint
UInt32 AnalogItemType Waiting time until transient interrup-
tion
BufferWaitTimeClientShutdown-
Setpoint
UInt32 AnalogItemType Wait time after shutting down the
client ended
BufferDischargeSequenceSelec-
tionSetpoint
Byte AnalogItemType Discharge selection
• 0 … alternating discharge
• 1 … UPS8600[1]
• 2 … UPS8600[2]
BufferChargeBeforeOutputEnable-
Setpoint
Boolean PropertyType Charge the buffer components
before activating the outputs
BufferStartOnlyOut-
put1FromBatterySetpoint
Boolean PropertyType When starting from the battery,
only switch on output 1
7.8.6.6
General
Display name
Data type
Definition
Description
DeviceCurrentThresholdSetpoint Byte AnalogItemType Threshold for system output cur-
rent prewarning
DeviceManualCurrent
ThresholdSetpoint
Byte AnalogItemType General prewarning threshold for
individual output current in
MANUAL mode
DevicePowerSupplyFailureDead-
TimeSetpoint
UInt16 AnalogItemType Dead time for alarm message 'In-
put voltage outside permitted
range'
DevicePrioritizedBuff-
eringOutput1EnableSetpoint
Boolean PropertyType Prioritized buffering of output 1.
DeviceSoftOutputCharacteris-
ticSetpoint
Boolean PropertyType Soft output characteristic
DeviceStartupModeSetpoint Byte MultiStateDiscrete-
Type
System start characteristics.
DeviceSystemOv-
erloadAlarmDeadTimeSetpoint
UInt16 AnalogItemType Dead time for system output cur-
rent prewarning.

Table of Contents

Other manuals for Siemens SITOP PSU8600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SITOP PSU8600 and is the answer not in the manual?

Siemens SITOP PSU8600 Specifications

General IconGeneral
BrandSiemens
ModelSITOP PSU8600
CategoryPower Supply
LanguageEnglish

Related product manuals