Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
238 Manual, 09.2018, A5E36758446-5-76
Reading and writing data sets
7.6.2.1
Overview of reading and writing data sets
An overview of all of the data sets, which are communicated between the power supply
system and PROFINET IO-Controller, is listed in the following tables. Here, a distinction is
made between the following data sets:
●
Data that is sent from the SITOP PSU8600, expansion modules, the
buffer modules and the UPS modules to the PROFINET IO-Controller .
●
Data that is sent from the PROFINET IO-Controller to the
SITOP PSU8600, the expansion modules, the buffer modules and the UPS modules.
Additional information about the individual data sets is provided in the corresponding
subchapters.
You can find information about the write behavior SITOP PSU8600 in mode STOP or RUN in
Section "Parameter write behavior of the SITOP PSU8600 (Page 348)".
Reading and writing data sets SITOP PSU8600
1 0 1
General remote values Reading General settings of
10 bytes
Writing Adjustable parameters for generally
configuring the SITOP PSU8600.
10 bytes
1 0 3 Output1 remote target
values
Reading Configuring output 1 of the
10 bytes
Writing Adjustable parameters for output 1 of
10 bytes
Information about the SITOP PSU8600.
7 0 1 Hardware settings Reading Hardware settings of
the SITOP PSU8600 (settings that were
made at the front of the device).
60 bytes
8 0 1 Buffer handling values
Configuring the buffer behavior.
Writing Adjustable parameters for the buffer
24 bytes
16 0 1 SITOP command
interface
Writing Function interface to execute special
functions not covered by the configura-
tion software or not able to be accessed
6 bytes
Result of SITOP com-
mand interface
Reading Status of processing the requested
function call of the "SITOP command
4 bytes
32 0 1 State information Reading Status information about
the SITOP PSU8600.
32 bytes
33 0 1 Actual buffer state
Reading Status information about the buffer
12 bytes
48 0 1 PROFIenergy values Reading PROFIenergy settings of
36 bytes