Parameter Details
2
2.5 d: References
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 231
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
When A1-02 = 6 [Control Method Selection = AOLV/PM], the drive sets o1-03 = 1 [0.01% (100% = E1-04)].
This parameter sets the frequency reference of Multi-Step Speed 15.
d1-16: Reference 16
No.
(Hex.)
Name Description
Default
(Range)
d1-16
(0291)
RUN
Reference 16
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
When A1-02 = 6 [Control Method Selection = AOLV/PM], the drive sets o1-03 = 1 [0.01% (100% = E1-04)].
This parameter sets the frequency reference of Multi-Step Speed 16.
d1-17: Jog Reference
No.
(Hex.)
Name Description
Default
(Range)
d1-17
(0292)
RUN
Jog Reference
Sets the Jog frequency reference in the units from o1-03 [Frequency Display Unit Selection]. Set H1-
xx = 6 [MFDI Function Select = Jog Reference Selection] to use the Jog frequency reference.
6.00 Hz
(0.00 - 590.00 Hz)
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
When A1-02 = 6 [Control Method Selection = AOLV/PM], the drive sets o1-03 = 1 [0.01% (100% = E1-04)].
d2: Reference Limits
d2 parameters set the upper and lower frequency limits to control the motor speed. Apply these parameters to for
example, run the motor at low-speed due to mechanical strength concerns, or if the motor should not be run at low
speed because of lubrication issues with the gears and bearings.
The upper frequency limit is set in d2-01 [Frequency Reference Upper Limit] and the lower limit is set in d2-02
[Frequency Reference Lower Limit].
Figure 2.44 Upper and Lower Frequency Limits
d2-01: Frequency Reference Upper Limit
No.
(Hex.)
Name Description
Default
(Range)
d2-01
(0289)
Frequency Reference Upper
Limit
Sets maximum limit for all frequency references. The maximum output frequency is 100%.
100.0%
(0.0 - 110.0%)
When the frequency reference is more than the value set in d2-01 the drive will continue to operate at the value set in
d2-01.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA GA500 GA50U Series and is the answer not in the manual?

YASKAWA GA500 GA50U Series Specifications

General IconGeneral
TypeDC Drive
ManufacturerYASKAWA
DimensionsVaries by model
WeightVaries by model
SeriesGA50U
Control MethodVector Control, V/f Control
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overload, Overtemperature, Short Circuit
Communication InterfaceEtherNet/IP
Ambient Temperature-10°C to +50°C
Humidity5% to 95% (non-condensing)
Storage Temperature-20°C to +60°C (-4°F to +140°F)

Related product manuals