3.7 Fine Tuning during Test Runs (Adjust the Control Function)
484 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
Open Loop Vector Control for PM Motors
Table 3.17 Parameters for Fine Tuning the Drive (A1-02 = 5 [OLV/PM])
Issue Parameter Number Possible Solutions Default Recommended Setting
Unsatisfactory motor performance
E1-xx parameters, E5-xx
parameters
Check the settings for E1-06,
E1-04 [Base Frequency,
Maximum Output Frequency].
Check the E5-xx and make sure
that you set all motor data
correctly.
Note:
Do not set E5-05 [PM Motor
Resistance (ohms/phase)] to a
line-to-line resistance value.
Do Auto-Tuning.
- -
Unsatisfactory motor torque and
speed response
n8-55 [Motor to Load Inertia
Ratio]
Adjust to align the load inertia
ratio of the motor and machine.
0 Near the load inertia ratio.
n8-45 [Speed Feedback Detection
Gain]
Decrease the setting value in
increments of 0.05.
0.80 -
C4-01 [Torque Compensation
Gain]
Adjust the setting value.
Note:
If you set this value too high, it
can cause overcompensation
and motor oscillation.
0.00 1.00
Oscillation when the motor
starts.
Motor stalls.
n8-51 [Pull-in Current @ Accel/
Decel]
Increase the setting value in
increments of 5%.
50% -
b2-02 [DC Injection Braking
Current]
b2-03 [DC Inject Braking Time
at Start]
Use DC Injection Braking at start.
Note:
This can cause the motor to
rotate in reverse for
approximately 1/8 of a turn at
start.
b2-02: 50%
b2-03: 0.00 s
b2-02: Adjust as necessary.
b2-03: 0.5 s
n8-55 [Motor to Load Inertia
Ratio]
Increase the setting value.
Note:
When you operate a single
motor or with a minimum
quantity of inertia, if you set
this value too high, it can cause
motor oscillation.
0 Near the load inertia ratio.
There is too much current during
deceleration.
n8-79 [Pull-in Current at
Deceleration]
Set n8-79 < n8-51.
50%
Note:
When n8-79 = 0, the drive will
apply the n8-51 setting to the
pull-in current during
deceleration.
Decrease in increments of 5%.
Stalling or oscillation occurs when
you apply the load during constant
speed
n8-47 [Pull-in Current Comp Filter
Time]
Decrease the setting value in
increments of 0.2 s.
5.0 s -
n8-48 [Pull-in/Light Load Id
Current]
Increase the setting value in
increments of 5%.
30% -
n8-55 [Motor to Load Inertia
Ratio]
Increase the setting value.
Note:
When you operate a single
motor or with a minimum
quantity of inertia, if you set
this value too high, it can cause
motor oscillation.
0 Near the load inertia ratio.
Hunting or oscillation
n8-45 [Speed Feedback Detection
Gain]
Increase the setting value in
increments of 0.05.
0.80 -
The drive detects STPo [Motor
Step-Out Detected] fault when the
load is not too high.
E5-09 [PM Back-EMF Vpeak
(mV/(rad/s))]
E5-24 [PM Back-EMF L-L
Vrms (mV/rpm)]
Adjust the setting value.
Examine the motor code on the
motor nameplate or the data
sheet, then set correct values for
E5-09 or E5-24.
*1
Yaskawa motor
Set the motor code from the
motor nameplate.
Motor from another
manufacturer
Set the values from the test
report.
The drive detected stalling or STPo
[Motor Step-Out Detected] at high
speed and maximum output
voltage.
n8-62 [Output Voltage Limit
Level]
Set to a value lower than the actual
input voltage.
200.0 V
400.0 V
-
*1 The default setting changes when the settings for E5-01 [Motor Code Selection] and o2-04 [Drive Model (KVA) Selection] change.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA GA500 GA50U Series and is the answer not in the manual?

YASKAWA GA500 GA50U Series Specifications

General IconGeneral
TypeDC Drive
ManufacturerYASKAWA
DimensionsVaries by model
WeightVaries by model
SeriesGA50U
Control MethodVector Control, V/f Control
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overload, Overtemperature, Short Circuit
Communication InterfaceEtherNet/IP
Ambient Temperature-10°C to +50°C
Humidity5% to 95% (non-condensing)
Storage Temperature-20°C to +60°C (-4°F to +140°F)

Related product manuals