Parameter Details
2
2.10 n: Special Adjustment
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 405
2.10 n: Special Adjustment
n parameters set these functions:
Function to prevent hunting
High-slip braking
Motor line-to-line resistance online tuning
Fine-tune the parameters that adjust motor control
n1: Hunting Prevention
The Hunting Prevention function will not let low inertia or operation with a light load cause hunting. Hunting
frequently occurs when you have a high carrier frequency and an output frequency less than 30 Hz.
n1-01: Hunting Prevention Selection
No.
(Hex.)
Name Description
Default
(Range)
n1-01
(0580)
Hunting Prevention
Selection
Sets the function to prevent hunting.
0
( 0, 1 )
Note:
When you replace a V1000-series drive with a GA500 drive, set n1-01 = 1 [Hunting Prevention Selection = Enabled].
When drive response is more important than the decrease of motor vibration, disable this function.
0 : Disable
1 : Enabled
n1-02: Hunting Prevention Gain Setting
No.
(Hex.)
Name Description
Default
(Range)
n1-02
(0581)
Expert
Hunting Prevention Gain
Setting
Sets the performance of the hunting prevention function. Usually it is not necessary to change this
parameter.
1.00
(0.00 - 2.50)
Adjust this parameter in these conditions:
When n1-01 = 1 [Hunting Prevention Selection = Enabled (Normal)], if oscillation occurs when you operate a
motor with a light load, increase the setting value in 0.1-unit increments.
When n1-01 = 2, if the motor stalls, decrease the setting value in 0.1-unit increments.
n1-03: Hunting Prevention Time Constant
No.
(Hex.)
Name Description
Default
(Range)
n1-03
(0582)
Expert
Hunting Prevention Time
Constant
Sets the primary delay time constant of the hunting prevention function. Usually it is not necessary to
change this parameter.
Determined by o2-04
(0 - 500 ms)
Adjust this parameter in these conditions:
Load inertia is large: Increase the setting value. If the setting value is too high, response will be slower. Also, there
will be oscillation when the frequency is low.
Oscillation occurs at low frequencies: Decrease the setting value.
n1-05: Hunting Prevent Gain in Reverse
No.
(Hex.)
Name Description
Default
(Range)
n1-05
(0530)
Expert
Hunting Prevent Gain in
Reverse
Sets the performance of the hunting prevention function. This parameter adjusts Reverse run. Usually
it is not necessary to change this parameter.
0.00
(0.00 - 2.50)
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA GA500 GA50U Series and is the answer not in the manual?

YASKAWA GA500 GA50U Series Specifications

General IconGeneral
TypeDC Drive
ManufacturerYASKAWA
DimensionsVaries by model
WeightVaries by model
SeriesGA50U
Control MethodVector Control, V/f Control
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overload, Overtemperature, Short Circuit
Communication InterfaceEtherNet/IP
Ambient Temperature-10°C to +50°C
Humidity5% to 95% (non-condensing)
Storage Temperature-20°C to +60°C (-4°F to +140°F)