Voyager™ III 528
Address Rotary Hex Switches (for I/O only)
For I/O Expansion Interface (no Axes being used): SW1 = 7, SW2 = 0
Programming Port
This is for factory use only. Used when E2 code is displayed (see error codes below).
Dip Switch Settings
Fiber Optic Light Level:
Location SW3
Low Level (0-15 meters): 1 = OFF, 2 = OFF
Medium Level (15-30 meters): 1 = ON, 2 = OFF (Default setting)
High Level (30-45 meters): 1 = OFF, 2 = ON
MAximum Level (>45 meters): 1 = ON, 2 = ON
Baud Rate:
Location SW3
16 MBAUD 3 = ON, 4 = ON (Default setting)
8 MBAUD 3 = ON, 4 = OFF
4 MBAUD 3 = OFF, 4 = ON
2 MBAUD 3 = OFF, 4 = OFF
Reserved:
Location SW3
5 = OFF, 6 = OFF, 7 = OFF, 8 = OFF
Flash Write Jumpers (not present on later revisions):
Location SW4
1 = ON, 2 = ON
Reset Button (not present on later revisions) :
SW5 – Press to reset card
Error Codes:
E1 Display Code = "Voltage or Temperature Error Detected!"
Displayed if voltage or temperature sensors on Field Interface board indicate an error. Please check
power supply, wiring and connections.
E2 Display Code = "Bad Checksum for SMCC Software!"
Displayed if checksum for SERCOS Slave Flash Program is not correct. Program needs to be
reloaded using the Serial Port connection.
E3 Display Code = "Wrong Interface Board Detected for Selected SERCOS Address!"
Displayed if the selected SERCOS Slave Address/SERCOS Slave mode does not match the Field
Interface functionality. For example, using an HPR Field Interface with a SERCOS Slave card set to
Drive Address 1-12 is not possible, since these are axes SERCOS addresses only, not peripheral I/O
SERCOS addresses.