6
-
Required space for maintenance and air flow Minimum allowable space to the obstacles
Unit:mm
Mark
123
L1 Open Open 500
L2 300 5 Open
L3 150 300 150
L4 555
Installation
type
L
2
L
3
L
4
L
1
Air
inlet
Air inlet
Air outlet
Maintenance
space
Unit: mm
2.2 Exterior dimensions
Models All models
Notes:
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more than 15mm.
(3) Where the unit is subject to strong winds, lay it in such a direction that
the blower outlet faces perpendicularly to the dominant wind direction.
(4) Leave a 1m or larger space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
(6) The unit name plate is attached on the lower right corner of the front
panel.
Z
51
40
36
100
845
10
11050
195
242
279
970
50 15
55
5027
52
11050
195
B
B
A
A
Terminal block
F
C
C
VIEW Z
C
5015
7050
150
40
F
E
370 4040
410 2020
55
60
388262
38
60
190 580 200
60 15
103 15
C
D
Mark Item
Service valve connection (gas side)
Service valve connection (liquid line)
Pipe/cable draw-out port
Drain discharge port
Anchor bolt hole
Cable draw-out port
A
B
C
D
E
F
ø5/8" (15.88) (flare)
ø3/8" (9.52) (flare)
4 places
ø20 x 3 places
M10 x 4 places
ø30 x 3 places

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDT45KXE6 and is the answer not in the manual?

Mitsubishi Heavy Industries FDT45KXE6 Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDT45KXE6
CategoryAir Conditioner
LanguageEnglish

Related product manuals