277
(2) Operation control function by the indoor controller
(1) Operations of functional items during cooling/heating [Applicable model: All models]
Cooling Heating
Dehumidify
Fan
Operation
Functional item
Thermostat
ON
Thermostat
ON
Thermostat
OFF
Thermostat
OFF
Hot start
(Defrost)
Compressor
4-way valve
Outdoor fan
Indoor fan
Louver motor
Drain pump
(4)
/
(2)
(2)
/
/
/
/
/
(2)
()
()
/
/
/
/
/
/
Thermostat ON:
Thermostat OFF:
(2)
Note (1) : Operation : Stop /: Turned ON/OFF by the control other than the room temperature control.
(2) ON during the drain motor delay control
(3) Drain pump ON setting may be selected by the indoor unit function setting of the wired remote controller. Refer to page 263 for details.
(2) Dehumidifying operation
(a) When the humidity sensor is not provided (Models other than FDT Series)
Intake air temperature sensor [Th
I-A (by the remote controller when the remote control sensor is enabled)] controls the
indoor temperature environment simultaneously.
1) Operation is started in the cooling mode. When the difference between the intake air temperature and the setting
temperature is 2°C or less, the indoor unit fan tap is brought down by one tap. That tap is retained for 3 minutes
after changing the indoor fan tap.
2) If the suction air temperature exceeds the setting temperature 3°C or more during defrosting operation, the indoor
fan tap is raised by one tap. That tap is retained for 3 minutes after changing the indoor fan tap.
3) If the thermostat OFF is established during the above control, the indoor fan tap at the thermostat ON is retained so
far as the thermostat is turned OFF.
4) After stopping the cooling operation, the indoor unit continues to run at Lo for 15 seconds.
(b) When the humidity sensor is provided (FDT Series only) [Optional]
1) Operation starts in the cooling mode, and the target relative humidity is determined based on the setting temperature.
If the humidity detected by the humidity sensor becomes lower than the target relative humidity, the indoor unit fan
tap is retained.
2) Anything other than 1) above is same as the item (a) above.
(3) Timer operation [Applicable model: All models]
(a) Timer
Set the duration of time from the present to the time to turn off the air-conditioner.
It can be selected from 10 steps in the range from “OFF 1 hour later” to “OFF 10 hours later”. After the clock timer
setting, the remaining time is displayed with progress of time in the unit of hour.
(b) OFF timer
Time to turn OFF the air-conditioner can be set in the unit of 10 minutes.
(c) ON timer
Time to turn ON the air-conditioner can be set. Indoor temperature can be set simultaneously.
(d) Weekly timer
Timer operation (ON timer, OFF timer) can be set up to 4 times a day for each weekday.
(e) Timer operations which can be set in combination
Timer
OFF timer
ON timer
Weekly timer
Timer
OFF timer
ON timer
Weekly timer
Note (1) : Allowed : Not

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDT45KXE6 and is the answer not in the manual?

Mitsubishi Heavy Industries FDT45KXE6 Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDT45KXE6
CategoryAir Conditioner
LanguageEnglish

Related product manuals