NO
NO
YES
Is the
connection of intake air
temperature sensor connector
OK?
Are the
characteristics of intake air
temperature sensor
OK?
YES
15
10
5
0 10 30 4020 50
Temperature-resistance characteristic
Temperature sensor resistance (k
Ω
)
Temperature (°C)
Note (1) 22.5kΩ at -6
°C
5kΩ at 25
°C
Correct.

Connect
connector.
Defective intake air
temperature thermistor

Replace.
Defective indoor control
PCB

Replace.
(Defective intake air
temperature thermistor
input circuit)
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected by indoor intake air
temperature thermistor (Thi-A)
3
.
Condition of error displayed
• When the temperature sensor
detects -50°C or lower for
5 seconds continuously,
the compressor stops.
After 3-minute delay, the
compressor starts again
automatically, but if this
anomaly occurs again within
60 minutes after the initial
detection.
• Or if 48°C or higher is
detected for 5 seconds
continuously.
4. Presumable cause
• Defective intake air
temperature thermistor
connector
• Defective intake air
temperature thermistor
• Faulty indoor control PCB
Note: