22
-
(f) Duct connected-High static pressure type (FDU)
Item
kW
kW
W
CMM
kg 40
230 1
Hi: 25 Lo: 20 Hi: 34 Lo: 27
dB(A)
mm 295 850 650
Internal thermostat for fan motor.
Frost protection thermostat
Models
FDU71KXE6
7.1
FDU90KXE6
9.0
8.0
1 Phase 220-240V 50Hz
Electronic Expansion Valve
Direct line starting
Possible (on return duct)
Rubber sleeve(for fan motor)
Polyurethane foam
Flare piping
Connectable with VP20 (I.D. 20mm, O.D. 26mm)
Necessary (both Liquid & Gas lines)
Drain hose
Thermostat by electronics
mm(in)
Wired remote control switch (Optional:RC-E3)
Wireless kit (Optional:RCN-KIT3-E)
Hi: 41, Lo: 37
Louver fin & inner grooved tubing
Hi: 42, Lo: 37
10.0
280 1
63
350 1370 650
Item
Indoor air temperature Outdoor air temperature
Standards
ISO-T1
Operation
DB WB DB WB
Cooling*
1
27
Heating*
2
20
19 35
7
24
6
Centrifugal fan 2
Liquid line: 9.52(3/8"),Gas line: 15.88(5/8")
Nominal cooling capacity*
1
Nominal heating capacity*
2
Power source
Net weight
Starting method
Outside air intake
Air filter, Q'ty
Shock & vibration isolator
Insulation (noise & heat)
Room temperature control
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Motor
Air flow(Standard)
Exterior dimensions
Height Width Depth
Refrigerant equipment
Heat exchanger
Operation control
Operation switch
Installation data
Refrigerant piping size
Noise level
Safety equipment
(1) The data are measured at the following conditions.Notes
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 "UNITARY AIR-CONDITIONERS"
Refrigerant control
Air handling equipment
Fan type & Q'ty
Models FDU71KXE6, 90KXE6
Pa
Available static pressure
Standard:50, MAX:130
Installed on side
_
Drain pump
Built-in Drain pump