(2)
After the setting time has elapsed, the “Filter cleaning” is displayed and, after operating for 24 hours further (counted also during the stop), the unit stops.
(9) Auto swing control [Applicable model: FDT, FDTW (models equipped of the panel of auto swing), FDTS and
FDE(N)]
(a) Louver control
(i) Press the [Louver] button to operate the swing louver when the air conditioner is operating.
“Auto wind direction” is displayed for 3 seconds and then the swing louver moves up and down continuously.
(ii) To fix the swing louver at a position, press one time the [Louver] button while the swing louver is moving so that
four stop positions are displayed one after another per second.
When a desired stop position is displayed, press the [Louver] button again. The display stops, changes to show the
“Louver stop” for 5 seconds and then the swing louver stops.
(iii) Louver operation at the power on
The louver swings one time automatically (without operating the remote controller) at the power on.
This allows inputting the louver motor (LM) position, which is necessary for the microcomputer to recognize the
louver position.
Note (1) If you press the Louver button, the swing motion is displayed on the louver position LCD for 10 second. The display changes to the “Auto wind
direction” display 3 seconds later.
(b) Automatic louver level setting during heating
While hot start operation and heating thermostat OFF operation, the louver keeps the level position (In order to prevent
the cold draft) whether the auto swing switch is operated or not (auto swing or louver stop), The louver position display
LCD continues to show the display which has been shown before entering this control.
(c) Louver-free stop control
When the louver-free stop has been selected with the indoor function of wired remote controller “Louver control setting”,
the louver motor stops when it receives the stop signal from the remote controller. If the auto swing signal is received
from the remote controller, the auto swing will start from the position where it was before the stop.
Note (1) When the indoor function of wired remote controller “Louver control setting” has been switched, switch also the remote control function “Louver
control setting” in the same way.
(10) Compressor inching prevention control [Applicable model: All models]
(a) 3-minutes timer
When the compressor has been stopped by the thermostat, remote controller operation switch or anomalous condition, its
restart will be inhibited for 3 minutes. However, the 3-minute timer is invalidated at the power on.
(b) 3-minutes forced operation timer
• Compressor will not stop for 3 minutes after the compressor ON. However, it stops immediately when the thermostat is
turned OFF by the stop command by means of the ON/OFF switch or the change of operation mode.
• If the thermostat is turned OFF during the forced compressor operation in heating mode, the louver position (with the
auto swing) is returned to the level position.
Note (1) The compressor stops when it has entered the protective control.