268
-
(c) The range of temperature setting.
When shipped, the range of set temperature differs depending on the operation mode as below.
Heating : 16~30°C (55~86°F)
Except heating (cooling, fan, dry, automatic) : 18~30°C (62~86°F)
1) Upper limit and lower limit of set temperature can be changed with remote controller.
Upper limit setting: valid during heating operation. Possible to set in the range of 20 to 30°C (68 to 86°F).
Lower limit setting: valid except heating (automatic, cooling, fan, dry) Possible to set in the range of 18 to 26°C (62 to 79°F).
When you set upper and lower limit by this function, control as below.
a) When !2 TEMP RANGE SET, remote controller function of function setting mode is "INDN CHANGE" (factory setting),
[If upper limit value is set]
During heating, you cannot set the value exceeding the upper limit.
[If lower limit value is set]
During operation mode except heating, you cannot set the value below the lower limit.
b) When !2 TEMP RANGE SET, remote controller function of function setting mode is "NO INDN CHANGE"
[If upper limit value is set]
During heating, even if the value exceeding the upper limit is set, upper limit value will be sent to the indoor unit.
But, the indication is the same as the temperature set.
[If lower limit value is set]
During except heating, even if the value lower than the lower limit is set, lower limit value will be sent to the indoor unit.
But, the indication is the same as the temperature set.
2) How to set upper and lower limit value
a) Stop the air-conditioner, and press
, (SET) and , (MODE) button at the same time for over three seconds .
The indication changes to "FUNCTION SET ".
b) Press
button once, and change to the "TEMP RANGE " indication.
c) Press
(SET) button, and enter the temperature range setting mode.
d) Select "UPPER LIMIT
" or "LOWER LIMIT " by using button.
e) Press
(SET) button to fix.
f) When "UPPER LIMIT
" is selected (valid during heating)
1 Indication:
SET UP UPPER 30°C "
2 Select the upper limit value with temperature setting button . Indication example: "UPPER 26°C " (blink-
ing)
3 Press
(SET) button to fix. Indication example: "UPPER 26°C" (Displayed for two seconds)
After the fixed upper limit value displayed for two seconds, the indication will return to "UPPER LIMIT
".