Review address setting.
Replace indoor control
PCB.
2. Error detection method
Auto (remote controller) setting
and manual setting are mixed in
the address setting method for
indoor units
3
.
Condition of error displayed
Same as above
4. Presumable cause
Mistake in address setting for
indoor unit
Note:
Address setting method list (Figures in [ ] are for old superlink models)
Models for new superlink protocol Models for old superlink protocol
Indoor unit address setting
Outdoor unit
address setting
Indoor unit address setting
Outdoor unit
address setting
Indoor unit No. SW Outdoor unit No. SW Outdoor unit No. SW Indoor unit No. SW Outdoor unit No. SW Outdoor unit No. SW
Manual address setting
(New SL)
000-127 00-31 00-31
00-47 00-47 00-47
(Old SL)
[00-47] [00-47] [00-47]
Auto address setting for
single refrgerant system
(New SL)
000 49 49 49 49 49
(Old SL)
Auto address setting for
multiple refrgerant systems
(New SL)
000 49 00-31
Not available
(Old SL)
Not available