20 Start-up, control with I/O and ID run
How to start up the drive
How to start up the drive using the basic control panel
Safety
Do not start-up the drive unless you are a qualified electrician.
Read and obey the instructions in chapter Safety instructions at the beginning of the
Hardware manual of the drive. Ignoring the instructions can cause physical injury or death, or
damage to the equipment
Check the installation. See chapter Installation checklist in the Hardware manual of the
drive.
Make sure there that the active start command is not on (DI1 in factory settings, i.e.
ABB standard macro). The drive will start up automatically at power-up if the
external run command is on and the drive is in the remote control mode.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if
there is a risk of damage in case of an incorrect direction of rotation, or
•a Normal ID run is required during the drive start-up, when the load torque is higher than
20% or the machinery is not able to withstand the nominal torque transient during the ID
run.
General Information
The settings and examples referred in this chapter are with respect to the basic control
panel. For more information on basic control panel settings and menu details, see Quick
installation and start-up guide (3AXD50000042620) or ACS-BP-S basic control panel’s
users manual (3AXD50000032527 [English]).
If you are performing the procedure with assistant control panel, see ACS-AP-x assistant
control panels user’s manual (3AUA0000085685 [English]).

Table of Contents

Other manuals for ABB ACS560

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS560 and is the answer not in the manual?

ABB ACS560 Specifications

General IconGeneral
Frequency50/60 Hz
Control MethodScalar control
Protection FeaturesOvercurrent, overvoltage, undervoltage, short circuit
Communication InterfacesModbus RTU, Profibus DP, CANopen, Ethernet/IP
Enclosure RatingIP21
Ambient Temperature-10 to +50 °C
Input Voltage380 to 480 V AC
Cooling MethodAir cooling (natural convection or forced ventilation)

Related product manuals