354 Parameters
95.20 HW options word 1 Specifies hardware-related options that require differentiated
parameter defaults.
This parameter is not affected by a parameter restore.
0b0000
0b0000…0b1111 Hardware op tions c onfiguration word. 1 = 1
95.21 HW options word 2 Specifies more hardware-related options that require
differentiated parameter defaults. See parameter 95.20 HW
options word 2.
WARNING! An incorrect setting may cause the motor
to rush uncontrollably, or the brake chopper or resistor
to overload.
0b0000
0b0000…0b1111 Hardware op tions c onfiguration word. 1 = 1
95.200 Cooling fan mode Selects the fan control type. The fan control functionality
enables heat dissipation from the drive and avoids dust
accumulation in the drive.
Auto
Auto Controls the fan automatically according to the temperature
changes of the drive.
0
Always on Fan runs continuously with the maximum speed (50Hz). 1
96
96 System
Language selection; access levels; macro selection;
parameter save and restore; control unit reboot; user
parameter sets; unit selection.
96.01 Language Selects the language of the parameter interface and other
displayed information when viewed on the control panel.
Notes:
• Not all languages listed below are necessarily supported.
• This parameter does not affect the languages visible in the
Drive composer PC tool. (Those are specified under View
– Settings – Drive default language.)
Not selected
Not selected None. 0
No. Name/Value Description Def/FbEq16
Bit Name Value
0 Supply frequency
60 Hz
If you change the value of this bit, you have to do a complete reset to
the drive after the change. After reset you have to reselect the macro
to be used.
See section Differences in the default values between 50 Hz and
60 Hz supply frequency settings on page 371.0 = 50 Hz.
1 = 60 Hz.
1…12 Reserved
13 du/dt filter
activation
When active, an external du/dt filter is connected to the drive/inverter
output. The setting will limit the output switching frequency, and
force the fan of the drive/inverter module to full speed.
0 = du/dt filter inactive.
1 = du/dt filter active.
14…15 Reserved
Bit Name Value
0...4 Reserved
5 Bypass present 1 = Bypass is used.
6 Cabinet drive 0 = Inactive, 1 = Active. Only for drive frames R6 or larger.
7 Reserved 0 = Inactive, 1 = Active. Only for drive frames R6 or larger.
8...15 Reserved